Service Interface
AFD Operator Interface
Chiller information is tailored to operators, service
technicians, and owners. When operating a chiller, there is
specific information you need on a day-to-day basis—
setpoints, limits, alarm information, and reports.
When servicing a chiller, you need different information
and usually more of it—historic and active alarms,
configuration settings, and customizable control
algorithms, as well as operation settings.
By providing two different tools—one for daily operation
and one for periodic service—everyone has easy access to
pertinent and appropriate information.
Table 19. The following AFD information is available from within the DynaView™:
Tracer AdaptiView™ display or
DynaView display
MENU items
Units
Comments
Reports - Motor (AFD items)
AFD Frequency
Hz
AFD Speed
RPM
AFD Transistor Temp
F/C
Settings - Mode Overrides
OIL Pump Manual Control
Auto/On
Oil/refrigerant/(AFD water pump) manual control
Compressor Control Signal
Auto/Manual
Manual control allows the user to override the automatic signal
and manually drive the Compressor Control Signal from
0–100%. The limits and safeties remain active. The compressor
control signal controls a calculated combination vanes position
and drive speed for leaving water control signal.
Note:
Both motor report and mode overrides contain chiller content along with the AFD related items identified above.
Once the new AFDK is installed, some parameters settings
may need to be changed for proper operation. Please
contact Global Parts Technical Services to request a drive
parameter sheet. The drive parameter sheet will contain a
list of chiller-specific parameter settings that may be
directly loaded using TechView™ or Tracer™ TU. To
contact Global Parts Technical Services, send a message
to
. Please provide the
serial numbers for the chiller, control panel (if CH531 or
Tracer AdaptiView™ upgrade), and the AFDK when
making your request.
CH530/CH531 Operator Interface
The chiller’s DynaView™ is the operator interface for the
Adjustable Frequency Drive (AFD). For the operator’s day-
to-day operational information, DynaView displays up to
seven lines of data (English or SI units) simultaneously on
the 1/4 VGA touch-sensitive screen. Logically organized
groups of information—chiller modes of operation, active
diagnostics, settings, and reports put information
conveniently at your fingertips. The AFD status can be
viewed from the DynaView MOTOR Reports menu listing.
Refer to the appropriate chiller control
Operation and
Maintenance
manual for a detailed list.
TechView Chiller Service Tool (Laptop
Computer)
TechView™ is a portable laptop computer control panel
interface for the service technician or advanced operator.
When you need more detailed information about a Trane
chiller, connect your laptop computer (with the TechView
software installed in it) to the DynaView™ plug-in port.
The TechView software user interface provides access to
that particular machine’s configuration settings,
customizable limits, status, and up to 60 active or historic
diagnostics. Any PC that meets the system requirements
may download up-to the- minute DynaView and TechView
software from the Trane website:
TechView is utilized when a factory or startup setting
requires field alterations. The adjustable AFD settings
listed below are adjustable via TechView. All others are set
to defaults predetermined for this application as based on
laboratory testing.
Once the new AFDK is installed, some parameters settings
may need to be changed for proper operation. Please
contact Global Parts Technical Services to request a drive
parameter sheet. The drive parameter sheet will contain a
list of chiller-specific parameter settings that may be
directly loaded using TechView. To contact Global Parts
Technical Services, send a message to
. Please provide the serial
numbers for the chiller, control panel (if CH531 or Tracer
AdaptiView™ upgrade), and the AFDK when making your
request.