Figure 17.
Busbar installation on compressor motor
terminal board
1. Compressor motor terminal board
2. Remove motor terminal lugs (from all 6 terminals).
3. Install shorting busbars across the motor terminal
pairs as shown.
4. Motor terminal lugs reinstalled
Input Power and Control Wiring
36
AFDK-SVU01C-EN
Installing Unit-Mounted Output
Conductors
Unit-mounted drives are connected to the motor by
Flexibar conductors.
1. Verify shorting bus bars are installed on motor
terminals as described in
2. Verify Flexibar conductors are routed through the
provided magnetic choke.
3. The Flexibar connections to the motor terminals
should be torqued to 27ft·lb (36.6N·m); refer to
for configuration.
Figure 18.
Motor connection assembly