![Trane Tracer CH530 Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/trane/tracer-ch530/tracer-ch530_installation-operation-and-maintenance-manual_1149730051.webp)
AFDK Startup Procedure
AFDK-SVU01C-EN
51
Note:
You do not use a magnet to bind the AFD Starter
LLID.
d. On the Tracer TU or TechView screen, select the
“yes” button to indicate the LLID has been selected.
e. When properly bound, exit the binding view.
f. Perform any remaining startup items.
6. When ready, start the drive from the Tracer
AdaptiView™ display, or from the DynaView operator
interface of the CH530/531 panel.
7. Check the AFDK chiller drive response to the UC800 or
DynaView. Initially, the drive will go to 38 hertz and
stay there until the CenTraVac chiller vanes open
based on load. The drive will change the speed from
there based on load demand.
8. Document all information on the Startup log.