29
Quick Menu
The Quick Menu gives access to the 12 most important setup
parameters of the drive. After programming the Quick Menu items, the
drive will, in many cases, be ready for operation. The Quick Menu
Quick Menu
Parameter
Description
Item Number
Name
1
001 Language
Selects language used for all displays.
2
102 Motor Power
Sets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102,
Motor Power
, to convert HP to kW.
3
103 Motor Voltage
Sets output characteristics of drive based on voltage of motor.
4
104 Motor Frequency
Sets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency.
5
105 Motor Current
Sets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor.
6
106 Motor Nominal Speed
Sets output characteristics of drive based on nominal full load speed of
motor.
7
201 Minimum Frequency
Sets minimum controlled frequency at which motor will run.
8
202 Maximum Frequency
Sets maximum controlled frequency at which motor will run.
9
206 Ramp Up Time
Sets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
10
207 Ramp Down Time
Sets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
11
323 Relay 1 Function
Sets function of high voltage Form C relay.
12
326 Relay 2 Function
Sets function of low voltage Form A relay.
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the
following procedure.
1. Press Quick Menu key.
2. Use
t
and
u
keys to find parameter group to edit.
3. Use + and - keys to find parameter you chose to edit.
4. Press Change Data key.
5. Use + and - keys to select correct parameter setting. Or, to move
to digits within a number, use
t
and
u
arrows.
Flashing cursor
indicates digit selected to change.
6. Press Cancel key to disregard change, or press OK key to accept
change and enter new setting.
Example of Changing Parameter Data
Assume Parameter 206,
Ramp Up Time,
is set at 60 seconds. Change
the ramp up time to 100 seconds in accordance with the following
procedure.
1. Press Quick Menu key.
2. Press + key until you reach Parameter 206,
Ramp Up Time
.
3. Press Change Data key.
4. Press
t
key twice hundreds digit will flash.
5. Press + key once to change hundreds digit from 0 to 1.
6. Press
u
key to move cursor to tens digit.
7. Press - key until 6 counts down to 0 and setting for
Ramp Up
Time
reads 100 s.
8. Press OK key to enter new value into drive controller.
NOTE
Programming additional parameter functions
available through Extended Menu key is done
in accordance with same procedure as
described for Quick Menu functions.
parameters are described in the table below. A detailed description of
the functions are given in the Programming section of this manual. The
Quick Menu is activated by pressing the QUICK MENU key on the
control panel.