106
4..
Application Functions
#
Parameter
Factory Setting
Range
Changes
4-Setup
Conversion
Data
Description
During Operation
Index
Type
400
Reset Function
INFINITE AUTOMATIC
Yes
Yes
0
5
401
Automatic Restart Time
10 sec.
0 - 600 sec.
Yes
Yes
0
6
402
Flying Start
Fans=ENABLE, Pumps=DISABLE
Yes
Yes
-1
5
403
Sleep Mode Timer
OFF
0 - 300 sec.
Yes
Yes
0
6
404
Sleep Frequency
0 Hz
Min freq - Par. 405
Yes
Yes
-1
6
405
Wake up Frequency
60 Hz
Par. 404 - max freq
Yes
Yes
-1
6
406
Boost Setpoint
100%
0 - 200 %
Yes
Yes
0
6
407
Switching Frequency
Depends on the unit
3.0 - 14.0 kHz
Yes
Yes
2
5
408
Interference Reduction Method
ASFM
Yes
Yes
0
5
409
Function in Case of No Load
WARNING
Yes
Yes
0
5
410
Function at Phase Loss
TRIP
Yes
Yes
0
5
411
Function at Over Temp
TRIP
Yes
Yes
0
5
412
Trip Delay Overcurrent
OFF
0 - 60 sec.
Yes
Yes
0
5
413
Minimum Feedback
0.000
-999,999.999 - FB
MIN
Yes
Yes
-3
4
414
Maximum Feedback
100.000
FB
MIN
- 999,999.999
Yes
Yes
-3
4
415
Units Relating to Closed Loop
%
Yes
Yes
-1
5
416
Feedback Conversion
LINEAR
Yes
Yes
0
5
417
Feedback Calculation
MAXIMUM
Yes
Yes
0
5
418
Setpoint 1
0.000
Min to max fdbk.
Yes
Yes
-3
4
419
Setpoint 2
0.000
Min to max fdbk.
Yes
Yes
-3
4
420
PID Normal/Inverse Control
NORMAL
Yes
Yes
0
5
421
PID Anti Windup
ENABLE
Yes
Yes
0
5
422
PID Start-up Frequency
0 Hz
Min. to max. freq.
Yes
Yes
-1
6
423
PID Proportional Gain
0.30
0.00 - 10.00
Yes
Yes
-2
6
424
PID Integral Time
OFF
0.01 - 9999.00 s. (Off)
Yes
Yes
-2
7
425
PID Differentiation Time
OFF
0.0 (Off) - 10.00 sec.
Yes
Yes
-2
6
426
PID Differentiation Gain Limit
5.0
5.0 - 50.0
Yes
Yes
-1
6
427
PID Lowpass Filter Time
0.01
0.01 - 10.00
Yes
Yes
-2
6