12
Power Connections
1. Make all power connections with 75
o
C rated copper wiring.
2. Conduit entry must be from the bottom on all drives. Conduit entries
are provided on smaller drives. For drives with auxiliary
enclosures, refer to the dimensional drawings provided for conduit
entry locations.
3. To meet UL requirements, install the metal grounding plate in all
drives that have a plastic bottom. Install the grounding plate just
above the plastic bottom. Ground the metal plate to the chassis and
ground the conduit to the metal plate.
4. The conduit entries provide strain relief for the wires in drives
mounted in NEMA 1 or NEMA 12 enclosures. With chassis
mounted drives, the power and control wires must have strain
relief supplied by the installer.
D
O
NOT
rely on the terminal blocks to
provide strain relief.
All current ratings are in amps.
460 VAC Input Current/Wire Gage
550 - 600 VAC Input Current/Wire Gage
380 VAC Input Current/Wire Gage
Model
Drive Input
Current
Maximum
AWG
6002
2.3
10
6003
2.6
10
6004
3.8
10
6006
5.9
10
6008
8.8
10
6011
11.1
10
6016
16.6
6
6022
21.4
6
6027
26.3
6
6032
31.2
2
6042
39.9
2
6052
50.6
1/0
6062
60.4
1/0
6072
75
1/0
6100
92.4
3/0
6125
117
3/0
6150
134
4/0
6175
179
2 x 4/0
6225
226
2 x 4/0
6275
270
2 x 4/0
200 - 208 VAC Input Current/Wire Gage
Model
Drive Input
Current
Maximum
AWG
6002
6.3
10
6003
7.3
10
6004
10.4
10
6006
16.8
10
6008
23.8
6
6011
32.2
6
6016
48.3
6
6022
61.9
2
6027
78.2
2
6032
92.0
0
6042
117.0
1/0
6052
139.2
3/0
6062
165.5
4/0
Model
Drive Input
Current
Maximum
AWG
6002
2.8
10
6003
3.8
10
6004
5.3
10
6006
9.1
10
6008
12.2
10
6011
15
10
6016
24
6
6022
32.0
6
6027
37.5
6
6032
44
6
6042
60
2
6052
72
2
6062
89
2
6072
104
1/0
6102
145
2/0
6122
174
3/0
6150
206
2x1/0
6152
206
2x1/0
6172
256
2x1/0
6175
256
2x1/0
6222
317
2x3/0
6225
317
2x3/0
6272
366
2x4/0
6275
366
2x4/0
6350
467
3x1/0
6352
467
3x1/0
6400
584
3x3/0
6500
648
3x3/0
6550
734
3x4/0
Model
Drive Input
Current
Maximum
AWG
6002
2.5
10
6003
3.4
10
6004
4.8
10
6006
8.3
10
6008
10.6
10
6011
14
10
6016
21
6
6022
27.6
6
6027
34
6
6032
41
6
6042
53
2
6052
64
2
6062
77
2
6072
104
1/0
6102
128
2/0
6122
157
3/0
6150
185
2x1/0
6152
185
2x1/0
6172
236
2x1/0
6175
236
2x1/0
6222
304
2x3/0
6225
304
2x3/0
6272
356
2x4/0
6275
356
2x4/0
6350
431
3x1/0
6352
431
3x1/0
6400
526
3x3/0
6500
581
3x3/0
6550
668
3x4/0
WARNING
!
Induced Voltage!
Run output motor cables from multiple drives
separately. Induced voltage from output motor
cables run together can charge equipment
capacitors even with the equipment turned off
and locked out. Failure to run output motor
cables separately could result in death or
serious injury.
Current ratings are in Amps