CVRF-SVN005C-EN
The secondary CT used in the two transformer per phase is
shown in
. For a typical wiring diagram used for
wiring low voltage applications using dual CTs, two
transformers per phase, see
Figure 56. Secondary CT used with 5 amp primary CT, X13580266-01, TRR00975
72.0-108.0
TRR00448
TRR00975
150:05:00
150
2.5
1
108
86.4-129.6
TRR00448
TRR00975
180:05:00
180
2.5
1
129.6
96.0-144.0
TRR00448
TRR00975
200:05:00
200
2.5
1
144
120-180
TRR00449
TRR00975
250:05:00
250
2.5
1
180
144-216
TRR00449
TRR00975
300:05:00
300
2.5
1
216
168-252
TRR00449
TRR00975
350:05:00
350
2.5
1
252
192-288
TRR00450
TRR00975
400:05:00
400
2.5
1
288
240-360
TRR00450
TRR00975
500:05:00
500
2.5
1
360
288-432
TRR00450
TRR00975
600:05:00
600
2.5
1
432
336-504
TRR00451
TRR00975
700:05:00
700
2.5
1
504
384-576
TRR00451
TRR00975
800:05:00
800
2.5
1
576
480-720
TRR00451
TRR00975
1000:05:00
1000
2.5
1
720
480-720
TRR00655
TRR00975
1000:05:00
1000
4
1
720
576-864
TRR00499
TRR00975
1200:05:00
1200
2.5
1
864
576-864
TRR00655
TRR00975
1200:05:00
1200
4
1
864
720-1080
TRR00499
TRR00975
1500:05:00
1500
2.5
1
1080
720-1080
TRR00655
TRR00975
1500:05:00
1500
4
1
1080
864-1296
TRR00453
TRR00975
1800:5, X1-X2
1800
4
1
126
1008-1512
TRR00453
TRR00975
2100:5, X1-X3
2100
4
1
1512
1200-1800
TRR00453
TRR00975
2500:5, X1-X4
2500
4
1
1800
Table 10. CT specifications for two transformers per phase (continued)
Actual Motor
RLA (A)
Primary CT
Number
Second CT
Number
CT Ratio (A:A)
CT Rating (A)
Inside Dia.
(inches)
Primary Turns
CT Meter Scale
Front View / Primary
RED
BRN
Front View / Secondary
BLK
WHT
Bottom View
BLK
WHT
RED
BRN
Primary
Leads
Secondary
Leads
Schematic
RED
BROWN
BLACK
WHITE
Primary
Secondary
Содержание Symbio CVRF
Страница 43: ...Figure 57 Dual CT wiring example Starter Work CVRF SVN005C EN 43...