filter section and is connected to the RTM. A diagnostic
SERVICE signal is sent to the remote panel if the
pressure differential across the filters is at least 0.5" w.
c. The contacts will automatically open when the
pressure differential across the filters decrease to 0.4"
w.c. The switch differential can be field adjusted
between 0.17" w.c. to 5.0" w.c. ± 0.05" w.c.
High Duct Static Switch Option
The high duct static switch is field-mounted in the
ductwork or plenums with smoke dampers. It will
cause a manual reset diagnostic if the duct static
exceeds the pre-set static limit. The static limit is
adjustable at the HI.