SCXF-SVX01Q-EN
47
CV Unit Zone Sensor Options
BAYSENS108
Dual setpoint, manual/automatic changeover sensor
BAYSENS110
Dual setpoint, manual/automatic changeover sensor with system
function
BAYSENS108 and BAYSENS110
These zone sensor modules are for use with cooling/
heating constant volume units. They have four system
switch settings (heat, cool, auto, and off) and two fan
settings (on and auto).The zone sensor provides either
manual or automatic changeover control with dual
setpoint capability.
BAYSENS108 and BAYSENS110 features and system
control functions include:
•
System control switch to select heating mode
(HEAT), cooling mode (COOL), automatic selection
of heating or cooling as required (AUTO), or to turn
the system off (OFF).
•
Fan control switch to select automatic fan operation
while actively heating or cooling (AUTO), or
continuous fan operation (ON).
•
Dual temperature setpoint levers for setting desired
temperature. The blue lever controls cooling, and
the red lever controls heating.
•
Thermometer to indicate temperature in the zone.
This indicator is factory calibrated.
(Possible Schematic Designation: 5U29)
BAYSENS110 only function status indicator lights
include:
•
SYSTEM ON glows continuously during normal
operation, or blinks if system is in test mode.
•
COOL glows continuously during cooling cycles, or
blinks to indicate a cooling system failure.
•
HEAT glows continuously during heating cycles, or
blinks to indicate a heating system failure.
•
SERVICE blinks or glows to indicate a problem.
These signals vary depending on the particular
equipment being used.
(Possible Schematic Designation: 5U29)
Integrated Comfort Systems
Sensors for CV and VAV
Applications
CV and VAV Unit Zone Sensor Options
These zone sensor options are for use with cooling/
heating Integrated Comfort System (ICS) systems.
BAYSENS074
Zone temperature sensor with timed override and local
setpoint adjustment
This electronic analog sensor features single setpoint
capability and timed override with override
cancellation. BAYSENS074 features and system control
functions include:
•
Remote temperature sensing in the zone
•
A timed override button to move an ICS or a
building management system from its
“unoccupied” to “occupied” mode
•
Thumbwheel for local setpoint adjustment
•
A cancel button to cancel the “unoccupied
override” command
(Possible Schematic Designation: 5U23)