68
SCXF-SVX01Q-EN
Controls
Points List
RTM Module
Binary Inputs
•
Emergency stop
•
External auto/stop
•
Unoccupied/occupied
•
Dirty filter
•
VAV changeover with hydronic heat
Binary Outputs
•
VAV box drive max (VAV units only)
•
CV unoccupied mode indicator (CV units only)
•
Alarm
•
Fan run request
•
Water pump request (water-cooled only)
Analog Input
•
Airside economizer damper minimum position
Analog Output
•
Outside air damper actuator
Heat Module:
•
Analog output
GBAS Module
Binary Inputs
•
Demand limit contacts
Binary Outputs
•
Dirty filter relay
•
Refrigeration fail relay
•
Heat fail relay
•
Supply fan fail relay
•
Active diagnostics
Analog inputs
•
Occupied zone cooling setpoint
•
Occupied zone heating setpoint
•
Unoccupied zone cooling setpoint
•
Unoccupied zone heating setpoint or minimum
outside air flow setpoint
•
Supply air cooling setpoint
•
Supply air heating setpoint
•
Supply air static pressure setpoint
ECEM Module
Analog Inputs
•
Return air temperature
•
Return air humidity
IIn
n a
ad
dd
diittiio
on
n,, u
un
niittss w
wiitth
h a
a V
VO
OM
M h
ha
av
ve
e::
Binary Inputs
•
VOM mode A, unit off
•
VOM mode B, pressurize
•
VOM mode C, exhaust
•
VOM mode D, purge
•
VOM mode E, purge w/duct pressure control
Binary Output
•
V.O. relay
BCI-I option
For BACnet
®
Points List. refer to ACC-SVP01*-EN.
LCI-I Points List
Refer to the LonTalk
™
Communications Interface for
Intellipak and Commercial Self-Contained Integration
Guide, BAS-SVP02*-EN.
Phase Monitor
Unit is equipped with phase monitor in control box.
The phase monitor will protect against phase loss,
imbalance and reversal of line voltage. If a fault occurs,
the red LED will energize. While the fault condition is
present, the phase monitor interrupts the 115V control
circuit. If no faults are observed, a green LED will be
energized.
Unit Control Components
The self-contained unit is controlled by a
microelectronic control system that consists of a
network of modules. These modules are referred to as
unit control modules (UCM). In this manual, the
acronym UCM refers to the entire control system
network.
These modules perform specific unit functions using
proportional/integral control algorithms. They are
mounted in the unit control panel and are factory wired
to their respective internal components. Each module
receives and interprets information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request; i.e.,
economizing, mechanical cooling, heating, ventilation.
Following is a detailed description of each module’s
function.