Thermostat (TCONT402AN32DA)
This thermostat is a multi-stage 3 heat/2 cool, auto
changeover digital display thermostat. It is a
nonprogrammable, wall-mounted thermostat, and it can be
used for economizer operation.
CO
2
Sensor
This optional sensor can be added for Demand Control
Ventilation (DCV) functionality. On units with a low leak
economizer, configure the JADE controller by setting the
following parameters:
Setpoints Menu
DCV SET = desired CO
2
ppm to start DCV
VENTMAX = desired maximum position w/DCV and
occupied status (2-speed applications require LO and HI
settings)
VENTMIN = desired minimum position w/DCV and
occupied status (2-speed applications require LO and HI
settings)
ADVANCED SETUP Menu:
CO
2
ZERO = set to detector's start level
CO
2
SPAN = detector's max level minus start level
Attach the sensor to the CO
2
and "R" terminals (at
customer connections).
Note:
When using any 0-10 Vdc CO
2
sensor with the JADE
you will need to set CO
2
ZERO to 400 ppm and the
CO
2
SPAN to 1600 ppm in the ADVANCED SETUP
menu.
Occupancy Sensor
A customer-supplied occupancy sensor can also be added
to provide damper control based on occupied/unoccupied
conditions.
Low Leak Economizer Units
To configure the JADE controller, set:
SYSTEM SETUP menu: OCC = INPUT
Attach the occupancy sensor to the OCC SENSOR wire
and "R" terminal (at customer connections). The
occupancy sensor must utilize a normally open contact for
proper operation.
If an occupancy sensor is not used, another option to
controlling occupied and unoccupied status is to use the 'G'
input (fan is running). Connect the G input to the OCC
SENSOR wire (at customer connections). The controller
will then operate in the occupied mode every time the
indoor fan is running.
Initiation of Operating Modes - JADE
Controller
The JADE controller is able to initiate the following modes:
Compressor, Economizer, Fans, Heating System, and
Cooling System.
The Compressor mode is initiated by either the OAT going
above the DRYBLB SET setting or by the thermostat
initiating a call to cool when the damper is at 100% open.
The Economizer mode is controlled by the MAT getting
above the MAT SET setting while the OAT is below the
DRYBLB SET setting.
While the fans are not controlled by the controller, the Fan
mode is dependent on what state the system is in (OCC or
Y1 states will cause the damper to go to a LOW fan speed
damper setting, while Y2 or W states will cause the
controller to open the damper to the HIGH fan speed
damper setting). The Heating System mode requires an
input to the AUX2-1 terminal from the thermostat, and the
Cooling System mode requires an input to the Y2 IN and/or
the Y1 IN terminals from the thermostat.
Содержание Foundation GCC180-300
Страница 30: ...30 RT SVX51L EN Figure 31 Through the base gas piping installation Installation...
Страница 42: ...42 RT SVX51L EN Table 18 Unit data log continued schematic s connections Network ID Maintenance...
Страница 49: ...RT SVX51L EN 49 Notes...
Страница 50: ...50 RT SVX51L EN Notes...
Страница 51: ...RT SVX51L EN 51 Notes...