26
RT-SVX51L-EN
•
Flue Exhaust clear of any obstruction
Gas Heat Data
Table 3.
Gas heater operating data
Heating Input Rate—Btu/h
240,000
320,000
350,000
380,000
Minimum Supply Gas Pressure Natural/LP
5.0/11.0
5.0/11.0
4.5/11.0
5.5/11.0
Manifold Gas Pressure
3.2-3.5
3.2-3.5
3.2-3.5
3.2-3.5
Combustion Blower Suction Pressure (1
st
Stage)
-0.6 to -0.8
-0.6 to -0.8
-0.6 to -0.8
-0.6 to -0.8
Combustion Blower Suction Pressure (2
nd
Stage)
-1 to -1.3
-1 to -1.3
-1 to -1.3
-1 to -1.3
Minimum Flame Sensing Current
(a)
5.0 Micro Amps DC
Normal Sensing Current Range
8.0 to 16 Micro Amps DC
Flue Gas Temperature Rise
Above Ambient
300 to 450° F
Flue Gas Content - % CO
2
7.5 to 8.5% (Natural Gas)
8.5 to 9.5% (LP)
Minimum Supply Air Temperature Across Heat
Exchanger
40° F
(a)
A voltage reading across pens (V+) and (V-) is equatable to the flame sensing current. One volt equals one micro amp.
Table 4.
Piping
Length of Pipe (ft)
Iron Pipe Size (IPS) Inches
1/2" Pipe
3/4" Pipe
1" Pipe
1¼” Pipe
1½” Pipe
15
76
176
345
750
1220
30
52
120
241
535
850
45
43
99
199
435
700
60
38
86
173
380
610
75
77
155
345
545
Note:
Capacity of Pipe of Different Diameters and Lengths in Cu. Ft. Per Hr. with Pressure Drop of 0.3" and Specific Gravity of 0.60.
Table 5.
Specific gravity multipliers
Specific Gravity
Multipliers
0.50
1.10
0.55
1.04
0.60
1.00
0.65
0.96
Figure 28.
Schematic diagram for field gas piping to units
Field supplied ground
Union
6” MIN
Gas Supply Line
Gas shuttoff (Field Supplied
outside unit cabinet.)
Drip Leg
Unit Access Hole
To Gas Train
1/8” NPT Test Plug
Содержание Foundation GCC180-300
Страница 30: ...30 RT SVX51L EN Figure 31 Through the base gas piping installation Installation...
Страница 42: ...42 RT SVX51L EN Table 18 Unit data log continued schematic s connections Network ID Maintenance...
Страница 49: ...RT SVX51L EN 49 Notes...
Страница 50: ...50 RT SVX51L EN Notes...
Страница 51: ...RT SVX51L EN 51 Notes...