14

18-CD29D1-3

Installer’s Guide

REAR

SIDE

CUT

-OUT

ALTERNATE FILTER
CLIPS LOCATION

Optional horizontal filter conversion kits are BAYFLTR203
for 17 1/2"  width cabinets, BAYFLTR204 for 21" width
cabinets, and BAYFLTR205 for 24" width cabinets.  These
include filters and brackets necessary for horizontal filters.
In addition, optional door kit BAYFLTR206 is also available.
See Figures 20.

RETURN AIR FILTERS FOR UPFLOW FURNACE
IN HORIZONTAL CONFIGURATION

When the Upflow Furnace is installed in a horizontal configu-
ration, the filter must never be installed inside or outside the
cabinet directly above the blower assembly. See Figure 10
(page 11). Remote filter grilles may be used for homeowner
convenience or the filters may be installed in the duct work
upstream of the furnace.  See Figures 20 (page 13).

ALTERNATE UPFLOW
FILTER CLIP / BRACKET INSTALLATION - KIT09224

1. Determine the location to be used. The furnace cabinet

has dimples for location of the alternate furnace clips
(

Side return only

).  Pre-drill clearance holes with a

3/16" drill.  Bottom return holes are pre-drilled.

2. Install the clips in front and rear of the desired location

using the screws provided.  The filter clip with the leaf
spring mounts in the rear of the cabinet.  See Figure 21.

a

UNIT

SIZE

RETURN AIR

BOTTOM

SIDE

14-1/2"

CUT ON LINE DO NOT CUT

17-1/2"

DO NOT CUT

DO NOT CUT

21"

DO NOT CUT CUT ON LINE

24-1/2"

DO NOT CUT CUT ON LINE

TABLE 7

INSTALLING THE OPTIONAL FILTER

The filter may need to be cut to fit the unit depending on the
location of the return air filter.

A score line and the words “CUT HERE” are located on the
end of the filter.  If your application requires cutting the filter,
do so as indicted by the score mark.

Airflow

Airflow

s

Two high velocity type air filters are required for each down-
flow furnace.   Downflow furnace filters must be located
outside the furnace cabinet.  Typical installations are shown
in Figures 22 and 23. Tables 8 and 9 provide information for
installation of the filter retaining brackets shipped with
downflow furnaces.

d

i

TYPICAL DOWNFLOW FURNACE
RETURN AIR FILTER INSTALLATIONS

TABLE 8

TABLE 9

CABINET

WIDTH

RETURN

DUCT

WIDTH

FILTER ACCESS

OPENING -

DIMENSION "A"

FILTER ACCESS

OPENING -

DIMENSION "B"

14-1/2"

13-1/4"

12"

14"

17-1/2"

16-1/4"

15"

14"

21"

19-3/4"

19-1/2"

14"

24-1/2"

23-1/4"

22"

14"

CABINET

WIDTH

FILTER

SIZE

FILTER BRACKET

LOCATION *

14-1/2"

2 - 14X20X1

12-7/8"

17-1/2"

2 - 16X20X1

14-3/8"

21"

2 - 16X20X1

13-1/8"

24-1/2"

2 - 16X20X1

11-5/8"

* Location dimension is from end of duct to the screw holes for the bracket.

Optional door kit
BAYFLTR206

Содержание *DH1B040A9241A

Страница 1: ...erty and is to remain with this unit Please return to service information pack upon completion of work Installer s Guide __First letter may be A or T 1 8 CD2 9 D1 3 UPFLOW UH1 UPFLOW HORIZONTAL A34162...

Страница 2: ...horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage...

Страница 3: ...quipment to approximate location If damage to contents is found report the damage immediately to the de livering agency Codes and local utility requirements governing the installation of gas fired equ...

Страница 4: ...46 cm above the floor and the furnace must be located or protected to avoid physical damage from ve hicles IMPORTANT The furnace must be installed level The only allowable variation would be slightly...

Страница 5: ...NTAL ALL DIMENSIONS ARE IN INCHES 1 UH1D120A9601 REQUIRES 3 DIAMETER VENT PIPE UH1C100A9481 UH1D100A9601 REQUIRES 2 1 2 OR 3 DIAMETER VENT PIPE 2 DIAMETER OF VENT PIPE MAY BE LIMITED TO 2 1 2 OR 3 ON...

Страница 6: ...From Dwg C341885 Rev 7 DH1 OUTLINE DRAWING DOWNFLOW HORIZONTAL ALL DIMENSIONS ARE IN INCHES 12345 3617898 3618 8 36178 8 3617838 1234567689 74 123456 897 4 4 4 4 7 4 4 7 4 1234 6 897 4 4 4 49 7 49 4...

Страница 7: ...e or other combustible material other than wood flooring For vertical downflow application subbase BAYBASE 205 must be used between the furnace and combus tible flooring When the downflow furnace is i...

Страница 8: ...or craft rooms Furnaces installed near chemical storage areas Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus tion Permanent wave solutions...

Страница 9: ...commencing within 12 inches of the top and one commencing within 12 inches of the bot tom of the enclosure The openings shall communi cate directly or by ducts with the outdoors or spaces crawl or at...

Страница 10: ...the bottom All return air duct systems should provide for installa tion of return air filters 1 Determine the appropriate position to set the furnace in order to connect to the existing supply and ret...

Страница 11: ...the cloths before you start the furnace RETURN AIR FILTERS Filter and filter rack are not supplied with unit TYPICAL UPFLOW RETURN AIR FILTER INSTALLA TIONS These furnaces require high velocity type...

Страница 12: ...ace cabinet side See Figures 13 14 15 NOTE Remove the bottom front channel to install the filter rack in the 14 1 2 width cabinet furnaces Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw...

Страница 13: ...ide of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 13 14 16...

Страница 14: ...ter clip with the leaf spring mounts in the rear of the cabinet See Figure 21 a UNIT SIZE RETURN AIR BOTTOM SIDE 14 1 2 CUT ON LINE DO NOT CUT 17 1 2 DO NOT CUT DO NOT CUT 21 DO NOT CUT CUT ON LINE 24...

Страница 15: ...d lateral of the existing venting system as well as quantity and type of bends c Use the appropriate tables in the latest edition of the National Fuel Gas Code ANSI Z223 1 CAN CGA B149 1 Installation...

Страница 16: ...LE TEMPERATURE MARKING D2846 CPVC 41 212 ASTM D2846 F441 SCH 40 80 212 ASTM F441 F442 SDR SERIES 212 ASTM F442 ABS ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING D2661 SCH 40 DWV 180 ASTM D2661...

Страница 17: ...MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET Except adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the ma...

Страница 18: ...pt adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the maximum length limit shown in the table above See Note 7 below for exception The...

Страница 19: ...y is fully open on a minimum of two sides beneath the floor Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer s Installation Instructi...

Страница 20: ...he condition of a heated space HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent as shipped or as nondirect vent Installation must conform to national state and local code...

Страница 21: ...large enough to maintain pitch of vent and properly seal Use cement mortar seal on inside and outside of wall See Figure 31 VENTING THROUGH THE ROOF When penetrating roof with a 2 PVC vent pipe a 2 el...

Страница 22: ...SUPPLIED COMBUSTION AIR VENT ELBOW FIELD SUPPLIED VENT 1 1 2 BAYAIR30AVENTA 3 PIPING 2 2 1 2 or 3 PIPING REDUCING COUPLING FIELD SUPPLIED IF NEEDED SEAL ALL WALL CAVITIES BAYVENT200B c CAUTION The ve...

Страница 23: ...TICIPATED SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF SUPPORT FIELD SUPPLIED VENT m 6 Min 40 Inch Upflow or Downflow Furnace Slope 1 4 per ft Slope 1 4 per ft All horizontal pipes must be supported at a ma...

Страница 24: ...wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be con nected to chimney with separate entry...

Страница 25: ...detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installat...

Страница 26: ...low models all 120 000 BTU upflow models UH1C080A9601A and all downflow models LABEL SAYS TOP STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE WHEN THE FACTORY SUPPLIED OFF SET 2X3 REDUC...

Страница 27: ...ced blower and reposi tion into the other drain tap of the inducer which is lo cated 90 clockwise around the inducer Move the cap from that drain tap to the unused drain tap On upflow units plug the h...

Страница 28: ...NG A 1 STAGE HEATING THERMOSTAT NO COOLING Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet To drain opening If upflow furnace is installed over a finishe...

Страница 29: ...xternal electrical source is utilized OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From drawing B340388 Rv 2 SEE NOTE 8 FURNACE B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SE...

Страница 30: ...E 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B341422 Rev 3 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEAT 1 STAGE COO...

Страница 31: ...P LEG AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG GAS PIPING The upflow horizontal furnace is shipped standard for left side installation of gas pipin...

Страница 32: ...necessary For 1 Cu Ft Dial Gas Flow CFH Chart Flow Reading 2 For 1 2 Cu Ft Dial Gas Flow CFH Chart Flow Reading 4 For 5 Cu Ft Dial Gas Flow CFH 10X Chart Flow Reading 4 6 Multiply the final figure by...

Страница 33: ...481A 3 5 W C 11 0 W C DH1D110A9601A 4 5 W C 11 0 W C 5 Adjust gas heat by removing the adjustment regulator cover screw a To increase outlet pressure turn the regulator adjust screw clockwise b To dec...

Страница 34: ...Code ANSI Z223 1 NFPA 54 or National Standard of Canada Natural Gas and Propane Installation Code CSA 149 1 Installation of this furnace at altitudes above 2 000 ft 610m shall be made in accordance w...

Страница 35: ...e sensor hot surface igniter or main burner orifices have required removal of the cover TABLE 20 Orifice Twist Drill Size If Installed At Sea Level ALTITUDE ABOVE SEA LEVEL and Orifice Required At Oth...

Страница 36: ...ition See Figure 57 58 Disconnect the electrical supply to the unit CAUTION If this is done during the cold weather months provi sions must be taken to prevent freeze up of all water pipes and water r...

Страница 37: ...ndensate drain is blocked either by debris improper draining or by freezing condensate the pressure switch will receive a signal warning of the accumulation of condensate in the heat exchanger assembl...

Страница 38: ...38 18 CD29D1 3 Installer s Guide...

Страница 39: ...s or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure seitch problem c Inducer problem 4 Flashes Open High Limit Device 5 Flashes Flame sensed when no fl...

Страница 40: ...mprovement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Literature Order...

Отзывы: