HIGH ALTITUDE DERATE
Input ratings (BTUH) of these furnaces are based on
sea level operation and should not be changed at eleva-
tions up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input
rate (BTUH) shall be reduced 4% for each 1,000 ft.
above sea level. The furnace input rate shall be checked
by clocking the gas flow rate (CFH) and multiplying by
the heating value obtained from the local utility sup-
plier for the gas being delivered at the installed altitude.
Input rate changes can be made by adjusting the mani-
fold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas
for upflow models and min 3.0 - max 4.5 in. W.C. - Natu-
ral Gas for downflow models) or changing orifices (ori-
fice change may not always be required). If the desired
input rate can not be achieved with a change in mani-
fold pressure, then the orifices must be changed. LP in-
stallations will require an orifice change.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with the local codes, or in
the absence of local codes, the
National Fuel Gas Code,
ANSI Z223.1/ NFPA 54
or
National Standard of
Canada, Natural Gas and Propane Installation Code,
CSA 149.1
. Installation of this furnace at altitudes
above 2,000 ft. (610m) shall be made in accordance with
the listed high Altitude Conversion Kit available with
this furnace.
IMPORTANT:
Re-install the propane orifices to the same depth as the
orifices supplied with the equipment.
GAS FLOW IN CUBIC FEET PER HOUR
2 CUBIC FOOT DIAL
SEC. FLOW
SEC. FLOW
SEC. FLOW
SEC. FLOW
8
900
29
248
50
144
82
88
9
800
30
240
51
141
84
86
10
720
31
232
52
138
86
84
11
655
32
225
53
136
88
82
12
600
33
218
54
133
90
80
13
555
34
212
55
131
92
78
14
514
35
206
56
129
94
76
15
480
36
200
57
126
96
75
16
450
37
195
58
124
98
73
17
424
38
189
59
122
100
72
18
400
39
185
60
120
104
69
19
379
40
180
62
116
108
67
20
360
41
176
64
112
112
64
21
343
42
172
66
109
116
62
22
327
43
167
68
106
120
60
23
313
44
164
70
103
124
58
24
300
45
160
72
100
128
56
25
288
46
157
74
97
132
54
26
277
47
153
76
95
136
53
27
267
48
150
78
92
140
51
28
257
49
147
80
90
144
50
TABLE 18
Y
ROTATE THE FRONT
COVER INWARD
MAKING SURE THAT
ALL SIDE FLANGES
ARE OUTSIDE OF THE
BOX.
INSERT THE TOP
FLANGE OF THE FRONT
COVER UNDER THE LIP
INSIDE THE BOX
ALL SIDE FLANGES
MUST BE OUTSIDE OF
THE BOX
ROTATE THE FRONT
COVER AS SHOWN
Содержание *DH1B040A9241A
Страница 38: ...38 18 CD29D1 3 Installer s Guide...