18-CD29D1-3

17

Installer’s Guide

Seal 

VENT PIPE

with RTV sealant

Seal

 INLET AIR PIPE

with RTV sealant

Front of Furnace

VENT AND INLET AIR CONNECTIONS

f

Connection of the 

vent pipe

 to the vent collar should

also be accomplished using RTV type sealant. This type
sealant provides a connection which remains flexible
and can be separated in the future if service needs re-
quire the removal of the vent pipe for service or clear-
ance.  See Figure 24.

NOTE:
To ensure proper operation at the vent lengths indi-
cated, the combustion air inlet and vent terminals
should be in the same pressure zone. Terminating the
vent and inlet in different pressure zones will change
the maximum vent lengths and may cause nuisance
tripping of the pressure switch(es). The amount of
change can not be predicted. The selection of the inlet
and outlet terminal locations are the responsibility of
the designer/installer. If the installer chooses separate
pressure zones for the terminals, the combustion air
inlet termination must be in the higher (more positive)
pressure zone.

 MAXIMUM VENT LENGTH:

MODEL

DIRECT VENT (2 PIPE SYSTEM) -

MAXIMUM TOTAL EQUIVALENT FEET FOR

VENT AND INLET AIR PIPES (See Notes)

NONDIRECT VENT (1 PIPE SYSTEM) -MAXIMUM TOTAL                  
EQUIVALENT FEET FOR 

VENT PIPE ONLY (See Notes)

2" PIPE

& FITTINGS

2-1/2" PIPE

& FITTINGS

3" PIPE

& FITTINGS

4" PIPE

& FITTINGS

2" PIPE

& FITTINGS

2-1/2" PIPE

& FITTINGS

3" PIPE

& FITTINGS

4" PIPE

& FITTINGS

*UH1B040A9241A

60

80

100

130

50

80

80

130

*UH1B060A9361A

60

80

100

130

50

80

80

130

*UH1B080A9421A

40

80

100

130

30

80

80

130

*UH1C080A9601A

NOT ALLOWED

NOT ALLOWED

70

130

NOT ALLOWED

NOT ALLOWED

50

130

*UH1C100A9481A

NOT ALLOWED

NOT ALLOWED

90

130

NOT ALLOWED

NOT ALLOWED

70

130

*UH1D100A9601A

NOT ALLOWED

NOT ALLOWED

90

130

NOT ALLOWED

NOT ALLOWED

70

130

*UH1D120A9601A

NOT ALLOWED

NOT ALLOWED

50

130

NOT ALLOWED

NOT ALLOWED

30

130

 

NOTES:

    * - First letter may be "A" or "T"

 1. The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot
     horizontal or vertical straight pipe section connected before or after the elbow.
 2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).
    If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception).
    The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.
 3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED!  THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH
    (Vent or Inlet air pipes in two pipe systems).
 4. One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is
    equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.
 5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet.
    There is zero equivalent length for the BAYVENT200.
 6. Pipe adapters are field supplied.
 7. 4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.
 8. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical terminations.  IPEX 081216, IPEX 081218, and IPEX 081219 may only be used  for
    horizontal vent terminations.  Equivalent lengths are IPEX 196009 = 5 feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet.

UPFLOW/ HORIZONTAL VENTING TABLE

TABLE 11

IMPORTANT:

Products installed in Canada must use vent systems
that are certified to the Standard for Type BH Gas Vent-
ing Systems (ULC S636) for Class II-A venting systems
(up to 65°C).  Components of the vent system must not
be interchanged with other vent systems or unlisted
pipe or fittings.  Plastic components, specified prim-
ers, and glues must be from a single system manufac-
turer and not intermixed with other system
manufacturer's vent system parts.  In addition, the first
three feet of the vent pipe must be visible for inspec-
tion.

WARNING

!

CARBON MONOXIDE POISONING HAZARD
Do not replace any of the factory supplied venting
components with field fabricated parts.  Failure to fol-
low this safety warning exactly could result in dam-
aged vents, damaged components, carbon monoxide
poisoning, or death.

Содержание *DH1B040A9241A

Страница 1: ...erty and is to remain with this unit Please return to service information pack upon completion of work Installer s Guide __First letter may be A or T 1 8 CD2 9 D1 3 UPFLOW UH1 UPFLOW HORIZONTAL A34162...

Страница 2: ...horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage...

Страница 3: ...quipment to approximate location If damage to contents is found report the damage immediately to the de livering agency Codes and local utility requirements governing the installation of gas fired equ...

Страница 4: ...46 cm above the floor and the furnace must be located or protected to avoid physical damage from ve hicles IMPORTANT The furnace must be installed level The only allowable variation would be slightly...

Страница 5: ...NTAL ALL DIMENSIONS ARE IN INCHES 1 UH1D120A9601 REQUIRES 3 DIAMETER VENT PIPE UH1C100A9481 UH1D100A9601 REQUIRES 2 1 2 OR 3 DIAMETER VENT PIPE 2 DIAMETER OF VENT PIPE MAY BE LIMITED TO 2 1 2 OR 3 ON...

Страница 6: ...From Dwg C341885 Rev 7 DH1 OUTLINE DRAWING DOWNFLOW HORIZONTAL ALL DIMENSIONS ARE IN INCHES 12345 3617898 3618 8 36178 8 3617838 1234567689 74 123456 897 4 4 4 4 7 4 4 7 4 1234 6 897 4 4 4 49 7 49 4...

Страница 7: ...e or other combustible material other than wood flooring For vertical downflow application subbase BAYBASE 205 must be used between the furnace and combus tible flooring When the downflow furnace is i...

Страница 8: ...or craft rooms Furnaces installed near chemical storage areas Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus tion Permanent wave solutions...

Страница 9: ...commencing within 12 inches of the top and one commencing within 12 inches of the bot tom of the enclosure The openings shall communi cate directly or by ducts with the outdoors or spaces crawl or at...

Страница 10: ...the bottom All return air duct systems should provide for installa tion of return air filters 1 Determine the appropriate position to set the furnace in order to connect to the existing supply and ret...

Страница 11: ...the cloths before you start the furnace RETURN AIR FILTERS Filter and filter rack are not supplied with unit TYPICAL UPFLOW RETURN AIR FILTER INSTALLA TIONS These furnaces require high velocity type...

Страница 12: ...ace cabinet side See Figures 13 14 15 NOTE Remove the bottom front channel to install the filter rack in the 14 1 2 width cabinet furnaces Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw...

Страница 13: ...ide of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 13 14 16...

Страница 14: ...ter clip with the leaf spring mounts in the rear of the cabinet See Figure 21 a UNIT SIZE RETURN AIR BOTTOM SIDE 14 1 2 CUT ON LINE DO NOT CUT 17 1 2 DO NOT CUT DO NOT CUT 21 DO NOT CUT CUT ON LINE 24...

Страница 15: ...d lateral of the existing venting system as well as quantity and type of bends c Use the appropriate tables in the latest edition of the National Fuel Gas Code ANSI Z223 1 CAN CGA B149 1 Installation...

Страница 16: ...LE TEMPERATURE MARKING D2846 CPVC 41 212 ASTM D2846 F441 SCH 40 80 212 ASTM F441 F442 SDR SERIES 212 ASTM F442 ABS ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING D2661 SCH 40 DWV 180 ASTM D2661...

Страница 17: ...MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET Except adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the ma...

Страница 18: ...pt adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the maximum length limit shown in the table above See Note 7 below for exception The...

Страница 19: ...y is fully open on a minimum of two sides beneath the floor Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer s Installation Instructi...

Страница 20: ...he condition of a heated space HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent as shipped or as nondirect vent Installation must conform to national state and local code...

Страница 21: ...large enough to maintain pitch of vent and properly seal Use cement mortar seal on inside and outside of wall See Figure 31 VENTING THROUGH THE ROOF When penetrating roof with a 2 PVC vent pipe a 2 el...

Страница 22: ...SUPPLIED COMBUSTION AIR VENT ELBOW FIELD SUPPLIED VENT 1 1 2 BAYAIR30AVENTA 3 PIPING 2 2 1 2 or 3 PIPING REDUCING COUPLING FIELD SUPPLIED IF NEEDED SEAL ALL WALL CAVITIES BAYVENT200B c CAUTION The ve...

Страница 23: ...TICIPATED SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF SUPPORT FIELD SUPPLIED VENT m 6 Min 40 Inch Upflow or Downflow Furnace Slope 1 4 per ft Slope 1 4 per ft All horizontal pipes must be supported at a ma...

Страница 24: ...wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be con nected to chimney with separate entry...

Страница 25: ...detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installat...

Страница 26: ...low models all 120 000 BTU upflow models UH1C080A9601A and all downflow models LABEL SAYS TOP STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE WHEN THE FACTORY SUPPLIED OFF SET 2X3 REDUC...

Страница 27: ...ced blower and reposi tion into the other drain tap of the inducer which is lo cated 90 clockwise around the inducer Move the cap from that drain tap to the unused drain tap On upflow units plug the h...

Страница 28: ...NG A 1 STAGE HEATING THERMOSTAT NO COOLING Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet To drain opening If upflow furnace is installed over a finishe...

Страница 29: ...xternal electrical source is utilized OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From drawing B340388 Rv 2 SEE NOTE 8 FURNACE B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SE...

Страница 30: ...E 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B341422 Rev 3 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEAT 1 STAGE COO...

Страница 31: ...P LEG AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG GAS PIPING The upflow horizontal furnace is shipped standard for left side installation of gas pipin...

Страница 32: ...necessary For 1 Cu Ft Dial Gas Flow CFH Chart Flow Reading 2 For 1 2 Cu Ft Dial Gas Flow CFH Chart Flow Reading 4 For 5 Cu Ft Dial Gas Flow CFH 10X Chart Flow Reading 4 6 Multiply the final figure by...

Страница 33: ...481A 3 5 W C 11 0 W C DH1D110A9601A 4 5 W C 11 0 W C 5 Adjust gas heat by removing the adjustment regulator cover screw a To increase outlet pressure turn the regulator adjust screw clockwise b To dec...

Страница 34: ...Code ANSI Z223 1 NFPA 54 or National Standard of Canada Natural Gas and Propane Installation Code CSA 149 1 Installation of this furnace at altitudes above 2 000 ft 610m shall be made in accordance w...

Страница 35: ...e sensor hot surface igniter or main burner orifices have required removal of the cover TABLE 20 Orifice Twist Drill Size If Installed At Sea Level ALTITUDE ABOVE SEA LEVEL and Orifice Required At Oth...

Страница 36: ...ition See Figure 57 58 Disconnect the electrical supply to the unit CAUTION If this is done during the cold weather months provi sions must be taken to prevent freeze up of all water pipes and water r...

Страница 37: ...ndensate drain is blocked either by debris improper draining or by freezing condensate the pressure switch will receive a signal warning of the accumulation of condensate in the heat exchanger assembl...

Страница 38: ...38 18 CD29D1 3 Installer s Guide...

Страница 39: ...s or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure seitch problem c Inducer problem 4 Flashes Open High Limit Device 5 Flashes Flame sensed when no fl...

Страница 40: ...mprovement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Literature Order...