background image

Start-Up

32

CAUTION

The use of untreated or improperly treated water in unit 
coils may cause scaling, erosion, corrosion, algae, 
smile or other equipment damage. Consult a qualified 
water treatment specialist to determine if water 
treatment is required. The Trane Company assumes no 
responsibility for equipment damage caused by 
untreated or improperly treated water.

WARNING

Disconnect electrical power prior to access into a fan or 
ductwork. Even when locked out electrically, fans may 
cause injury or damage if the impeller is subject to 
“wind-milling.” The impeller should be secured to 
physically restrict rotational movement. Failure to 
secure impeller can cause severe personal injury or 
death. Disconnect electrical power source when 
connecting or disconnecting electrical wires for test 
procedures. Do not open service access doors while 
the unit is operating. Failure to exercise caution or while 
inspecting. unit operation may result in injury or death 
from electrical shock, air movement or rotating parts.

Start-up Procedures

After completing all start-up checks and procedures, the unit 
may be started. The following checks and adjustment should 
be made during initial start-up:

If the unit was stored for an extended period of time, the 
following items should be checked before starting the unit.

1.

2.

3.
4.

5.

6.

Maximum allowable voltage imbalance is two percent. Voltage 
imbalance is defined as 100 times the sum of the deviation of 
the three voltage from the average, divided by twice the 
amperage voltage. For example, if the three measured 
voltage are 221, 230, and 227, the average would be 226 
volts. The percent of voltage imbalance is then calculated:

In this example, 2.2 percent imbalance is not acceptable and 
the power company should be notified to correct it.

7.

8.

Perform the following steps prior to starting the unit.

1.

2.

Inspect electrical connections. They should be clean and 
secure. Compare actual wiring with specific diagrams 
provided on the unit.
Check piping and valves for leaks. Open or close the 
valves to check for proper operation. Drain lines should be 
open.

Inspect motor bearings for moisture and rust. Replace 
bearings if necessary and re-pack with new grease.
Check motor winding. An acceptable winding resistance 
reading is from 6 meg-ohms to infinity. If reading is less 
than 5 meg-ohms, winding should be dried out in an oven 
or by a blower.
Inspect the entire motor for rust and corrosion.
Lubricate the motor as instructed in the section titled 
“Periodic Maintenance”, or as indicated by the 
maintenance tag on the motor.
Bump-start unit and observe the fan wheel for proper 
rotation, as indicated by rotation arrow located on fan 
housing.
Measure the motor voltage and amperage on all phases to 
ensure proper operation. The readings should fall within 
the range given on the motor nameplate.

Check unit vibration if the fan speed is changed more than 
5% from the original designed rpm, or if parts such as 
shafts, fan wheels, bearings, or other drive components 
are replaced. Do not exceed max. fan rpm.
Pay particular attention to any vibration, noise or 
overheating of the motor and fan bearings. (Bearings may 
run warm during break in.)

3.

4.

5.

6.

7.

If equipped with a refrigerant coil, charge and leak-test the 
unit and get it ready for operation according to instructions 
provided with the condenser equipment.
Check that all air filters are in place and positioned 
properly. Under Periodic maintenance, see section titled 
“Air Filters”.
Close and secure all unit access doors. Check that the 
latch set screw are tight.
Remove all foreign material from the drain pan and check 
drain opening and condensate line for obstructions.
Prime the DRAIN TRAP.

100 x {[226-221]} + {[230-226[} + {[227-226]}
                                2 x 226
= 2,2% (unacceptable)

Содержание CLCP Euro 25

Страница 1: ...Installation Operation Maintenance Quantum Climate Changer Air Handlers Model CLCP Euro 25 CLCP Euro 50 CLCP Euro XP Airflow Range 1000 65 000 CFM 0 5 31 m s October 2018 IND SVN01A E4...

Страница 2: ...afe practices Indicates a situation that could result in equipment or property damage only accidents WARNING CAUTION NOTICE Important Environmental Concerns Important Responsible Refrigerant Practices...

Страница 3: ...se regulations supersede these policies Non Ingersoll Rand personnel should always follow local regulations WARNING Follow EHS Policies Copyright This document and the information in it are the proper...

Страница 4: ...ing Moving to Position On Site Forklift Truck Roller Movement LH RH Convention Foundation Erection Duct Connections External Connection Frame to Frame Connection Panel to Frame Connection Panelling Br...

Страница 5: ...QuantumTM Air Handler are Central Station Air Handlers designed for a variety of controlled air application The basic unit consists of a fan heating and or cooling coils filters and air dampers See pr...

Страница 6: ...Section 1 Type W WL 1 2 Tube H WLH 1 2 Tube A A 1 2 Tube L LL 1 2 Tube Q WLQ 1 2 Tube B AA 1 2 Tube D DL 1 2 Tube F FD 1 2 Tube S Special 21 Coil Connection L LH Side R RH Side B Both Sides X None 22...

Страница 7: ...rotected The warranty will not cover damages to the unit do to negligence during storage Indoor storage is ideal and requires only a few special precautions To protect the unit from damage due to the...

Страница 8: ...units must only be applied via the unit base frame or shipping pallet Rigging and Handling A specific lifting method for offloading the units is recommended as follows See Figure 2 1 2 3 4 5 Off Load...

Страница 9: ...Rigging and Handling 9 APPLICABLE ON ALL SECTION OTHER THAN SECTION WITH DRAINPAN APPLICABLE ON SECTION WITH DRAINPAN ONLY Figure 3 Lifting a coil section using a sling rope Figure 2...

Страница 10: ...In the case of larger units the use of several forklift trucks may be required Use extended fork lifting to prevent Drain pan damages during handling Base panel and structure damages Coil header and...

Страница 11: ...ure 9 gives recommended space allowances On the designated access side of the unit working areas must have minimum 1 mtr space P Allowance for coil connections dimension C must be dimension 200mm unit...

Страница 12: ...Heating and Air Conditioning System 90B Inlet and discharge air duct connections to the unit should be made with a flexible material minimizing noise and vibration Typically about three inches is need...

Страница 13: ...FOR CLCP 25mm FOR CLCP 50mm Assembly Installation CLCP EURO CLCP EURO XP External Connection BREAK POINT JOINING METHOD MODULE TO MODULE BREAK POINT EXTERNAL JOINING TO BE DONE AT JOB SITE 13...

Страница 14: ...Assembly Installation CLCP EURO 25 Breakpoint Frame to Frame OMS C0325_B CLCPEURO 25 Break Point Frame to Frame Joining 14...

Страница 15: ...Assembly Installation CLCP EURO 25 Breakpoint Panel to Frame OMS C0326_B CLCPEURO 25 Break Point Panel to Frame Joining 15...

Страница 16: ...Assembly Installation CLCP EURO 50 Breakpoint Frame to Frame 16 CLCPEURO 50 Break Point Frame to Frame Joining...

Страница 17: ...17 Assembly Installation CLCP EURO 50 Breakpoint Panel to Frame CLCPEURO 50 Break Point Panel to Frame Joining...

Страница 18: ...Assembly Installation CLCP EURO CLCP EURO XP Paneling 18...

Страница 19: ...19 Assembly Installation CLCP EURO XP Breakpoint ASSEMBLY INSTALLATION CLCPEURO XP BREAKPOINT INTERNAL JOINT TYPE1...

Страница 20: ...Assembly Installation CLCP EURO XP Breakpoint 20 ASSEMBLY INSTALLATION CLCPEURO XP STANDARD SECTION TO WIDER SECTION INTERNAL JOINT TYPE 2...

Страница 21: ...21 Assembly Installation CLCP EURO XP Breakpoint ASSEMBLY INSTALLATION CLCPEURO XP STANDARD SECTION TO WIDER SECTION INTERNAL JOINT TYPE 3...

Страница 22: ...Assembly Installation CLCP EURO XP CKD At Jobsite 22...

Страница 23: ...23 Assembly Installation CLCP...

Страница 24: ...Assembly Installation CLCP 24...

Страница 25: ...stallation CLCP Removing Replacing a motor CLCP 003 015 Removing shipping bracket non drive side CLCP 003 035 Apply Silicone along panel parameters prior to installing back the panel after removing sh...

Страница 26: ...the drain pan will likely overflow Figure 13 Drain Pan Trapping for module under Negative Pressure Figure 13 H 1 for each 1 of maximum negative pressure 1 J 1 2H L H J Pipe Diameter Insulation Unit Wi...

Страница 27: ...mmendation Refer to Figure 15 17 for typical cooling heating and steam coil piping Proper installation piping and trapping is necessary to assure satisfactory coil operation and to prevent operational...

Страница 28: ...as possible to the coil Vent the vacuum breaker line to the atmosphere or connect it to the return main at the discharge side of the steam trap Run the return pipe at the full size of the steam trap c...

Страница 29: ...d line OD and install it close to the condenser Minimize use of the other valves tube bends and reducers since these items tend to increase pressure drop and to reduce subcooling at the expansion valv...

Страница 30: ...cked To braze Thermostatic Expansion Valves TXV avoid direct flame figure 19 to the valve body and avoid excessive heat on diaphragm As an extra precaution a wet cloth may be around the body and eleme...

Страница 31: ...Piping and Connection Factory Supplied OFF Set Type Coil Flange Installation CLCP 030 050 For Double Coil In Single casing LL WL 4 Row Only 1 Flange Socket Weld Standard 2 Flange Socket Weld Offset Ty...

Страница 32: ...correct it 7 8 Perform the following steps prior to starting the unit 1 2 Inspect electrical connections They should be clean and secure Compare actual wiring with specific diagrams provided on the un...

Страница 33: ...USE FOR VIBRATION Fan RPM can be determined by using a strobe type tachometer or revolution counter Align the fan motor sheaves by using a straightedge The straightedge must be long enough to span the...

Страница 34: ...or ductwork Even when locked out electrically fans may cause injury or damage if the impeller is subject to wind milling The impeller should be secured to physically restrict rotational movement can...

Страница 35: ...1 gives recommended maintenance intervals for the CLCP unit Intervals are based upon normal running conditions in a moderate climate and assuming 24 hour running Units operating outside these guideli...

Страница 36: ...ion instruction Most smaller frame motors come without grease nipple where the bearings are permanently sealed The motor with double shielded bearings are lubricated for life and cannot be re lubricat...

Страница 37: ...directional arrows pointing in direction of airflow To clean permanent filters wash under a stream of water to remove dirt and lint Remove oil filter aluminium or grease filter with a wash of mild al...

Страница 38: ...r pulley or bushing installation wobbling and or damaged pulleys can unbalance a drive wear out belt rapidly and damage bearings and bend shafts Check and repair worn bearings and bent shafts Select r...

Страница 39: ...e component life and is based on fan brake horsepower requirement Check the belt tension as follows Measure the span length mm of the drive With a belt tensioner at the center of the span apply a forc...

Страница 40: ...Maintenance 40 Figure 20 Belt Tension Measurement...

Страница 41: ...th dirt preventing proper ventilation Overloaded motor Motor fan damaged Remove fan cover clean fan and replace cover Reduce load or replace with larger motor Replace motor fan clean Excessive vibrati...

Страница 42: ...Trouble Analysis 42...

Страница 43: ...43 Trouble Analysis Pulley and Belt...

Страница 44: ...Appendix A Fan and Arrangement 44 Fan Discharge Arrangement...

Страница 45: ...Appendix B Filter Layout and Quantity 45 Filter Dimension Nominal and Arrangement Flat Bag Cartridge Air Filter 6110 3130_2 page1...

Страница 46: ...Appendix B Filter Layout and Quantity 46 Filter Dimension Nominal and Arrangement Flat Bag Cartridge Air Filter 6110 3130_2 page2...

Страница 47: ...47 6110 3286_A Appendix B Filter Layout and Quantity Filter Dimension Nominal and Arrangement High Capacity Air Filter Angle Filter...

Страница 48: ...48 Appendix B Filter Layout and Quantity Filter Dimension Nominal and Arrangement HEPA AstroCel I HCX Filter 6110 3323_A...

Страница 49: ...49 6112 1853 Appendix B Filter Layout and Quantity Filter Dimension Nominal and Arrangement HEPA AstroCel VXL Filter...

Страница 50: ...Appendix B Filter Layout and Quantity Filter Dimension Nominal and Arrangement HEPA AstroCel VXL Filter 50...

Страница 51: ...Typical Motor Wiring Diagram 51...

Страница 52: ...52 Service Light and Door Switch Wiring...

Страница 53: ...Factory Installed VFD TR200 Wiring Setting 53...

Страница 54: ...Factory Installed VFD TR200 Wiring Setting 54 TR200 BASIC SETTING_OPEN LOOP...

Страница 55: ...lar maintenance of your installation by a specialist in our equipment Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious...

Страница 56: ...Pre Start Up Checklist 56...

Страница 57: ...Pre Start Up Checklist 57...

Страница 58: ...crease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Ing...

Отзывы: