Piping and Connection
Piping – Condensate Drain Pan
Connection
On cooling section(s) the drain pan should always be
connected directly to a trap to ensure proper drainage of
condensate.
WARNING
Failure to provide adequate condensate piping may
result in water damage to equipment or building.
Male-threaded, 1-1/2" BSPT condensate drain connection is
provided on one side of the coil section. The main drain lines
and trap must be the same size as the drain connection. Pitch
the connection line horizontal or downward toward an open
drain and install a plugged tee to facilitate cleaning. Conden-
sate lines should not be connected to a closed drain. This is to
avoid the possibility of drawing sewer gasses into the unit.
Drain traps must be primed. lf they are not, the trap is essen-
tially non-existent and the drain pan will likely overflow.
Figure 13 Drain Pan Trapping for module
under Negative Pressure
Figure 13
H = (1” for each 1” of maximum negative pressure) + 1”
J = 1/2H
L = H + J + Pipe Di Insulation
Unit With More Than 1 Drain Pan
With the Trane QuantumTM Air Handler, each module can be
ordered with or without a drain pan. When more than one
module has a drain pan, you must trap each module individu-
ally.
Connecting all drains to a common line with only one trap will
result in condensate retention, and possible water damage to
the air handler or adjoining space.
If a module has a drain pan for cleaning purposes only, it does
not need a trap; however a cap or shut off valve should be
installed on the drain connection. Only modules handling
condensate, such as a cooling coil module or eliminator
module, require a trap. Figure 13 through Figure 14 are
examples of typical installations.
26
Figure 14 Drain Pan Trapping for module
under Positive Pressure
Figure 14
K = min. ½”
H = ½” plus maximum total static pressure
Содержание CLCP Euro 25
Страница 16: ...Assembly Installation CLCP EURO 50 Breakpoint Frame to Frame 16 CLCPEURO 50 Break Point Frame to Frame Joining...
Страница 17: ...17 Assembly Installation CLCP EURO 50 Breakpoint Panel to Frame CLCPEURO 50 Break Point Panel to Frame Joining...
Страница 18: ...Assembly Installation CLCP EURO CLCP EURO XP Paneling 18...
Страница 22: ...Assembly Installation CLCP EURO XP CKD At Jobsite 22...
Страница 23: ...23 Assembly Installation CLCP...
Страница 24: ...Assembly Installation CLCP 24...
Страница 40: ...Maintenance 40 Figure 20 Belt Tension Measurement...
Страница 42: ...Trouble Analysis 42...
Страница 43: ...43 Trouble Analysis Pulley and Belt...
Страница 44: ...Appendix A Fan and Arrangement 44 Fan Discharge Arrangement...
Страница 50: ...Appendix B Filter Layout and Quantity Filter Dimension Nominal and Arrangement HEPA AstroCel VXL Filter 50...
Страница 51: ...Typical Motor Wiring Diagram 51...
Страница 52: ...52 Service Light and Door Switch Wiring...
Страница 53: ...Factory Installed VFD TR200 Wiring Setting 53...
Страница 54: ...Factory Installed VFD TR200 Wiring Setting 54 TR200 BASIC SETTING_OPEN LOOP...
Страница 56: ...Pre Start Up Checklist 56...
Страница 57: ...Pre Start Up Checklist 57...