Evaporator water connections are grooved.
•
Thoroughly flush all water piping to the unit before
making the final piping connections to the unit.
•
Components and layout will vary slightly,
depending on the location of connections and the
water source.
•
A vent is provided on the top of the evaporator at
the chilled water inlet. Be sure to provide additional
vents at high points in the piping to bleed air from
the chilled water system. Install necessary pressure
gauges to monitor the entering and leaving chilled
water pressures.
•
Provide shutoff valves in lines to the gauges to
isolate them from the system when they are not in
use. Use rubber vibration eliminators to prevent
vibration transmission through the water lines.
•
If desired, install thermometers in the lines to
monitor entering and leaving water temperatures.
•
Install a balancing valve in the leaving water line to
control water flow balance.
•
Install shutoff valves on both the entering and
leaving water lines so that the evaporator can be
isolated for service.
Evaporator Piping Components
Piping components include all devices and controls
used to provide proper water system operation and
unit operating safety. These components and their
general locations are given below.
Figure 15.
Typical water piping components
A
2
1
2
3
3
7
8
6
4
5
2
2
A
A
B
8
C
Item
Description
Item
Description
1
Bypass Valve
Pi
Pressure Gauge
2
Isolation Valve
FT
Water Flow Switch
3
Vibration Eliminator
T1
Evap Water Inlet Temp Sensor
4
Evaporator - End View (2-pass)
T2
Evap Water Outlet Temp Sensor
5
Evaporator Waterbox (2-pass)
NOTES
6
Vent
A
Isolate unit for initial water loop cleaning
7
Strainer
B
Vent must be installed at the high point of the line
8
Drain
C
Drain must be installed at the low point of the line
Entering Chilled Water Piping
•
Air vents (to bleed air from system).
•
Water pressure gauges with shutoff valves.
•
Vibration eliminators.
•
Shutoff (isolation) valves.
•
Thermometers (if desired).
•
Clean-out tees.
•
Pipe strainer.
Leaving Chilled water Piping
•
Air vents (to bleed air from system).
•
Water pressure gauges with shutoff valves.
•
Vibration eliminators.