Ascend
™
™
Model ACR
Installation Completion Check
Sheet and Request for Trane
Service
IIm
mp
po
orrtta
an
ntt:: A copy of this completed form must be
submitted to the Trane service agency that
will be responsible for the start-up of the
chiller. Start-up will NOT proceed unless
applicable items listed in this form have
been satisfactorily completed.
To:
Trane Service Office:
S.O. Number:
Serial Numbers:
Job/Project Name:
Address:
The following items
are being installed
and will be completed by:
IIm
mp
po
orrtta
an
ntt:: Start-up must be performed by Trane or an
agent of Trane specifically authorized to
perform start-up and warranty of Trane®
products. Contractor shall provide Trane
(or an agent of Trane specifically
authorized to perform start-up) with notice
of the scheduled start-up at least two weeks
prior to the scheduled start-up.
IIm
mp
po
orrtta
an
ntt:: IItt iiss rre
eq
qu
uiirre
ed
d tth
ha
att h
he
ea
atte
errss a
arre
e e
en
ne
errg
giizze
ed
d
ffo
orr a
a m
miin
niim
mu
um
m o
off 2
24
4 h
ho
ou
urrss p
prriio
orr tto
o sstta
arrtt
u
up
p.. T
Th
he
erre
effo
orre
e,, cch
hiilllle
err ssh
ho
ou
ulld
d h
ha
av
ve
e p
po
ow
we
err
ffo
orr tth
hiiss a
am
mo
ou
un
ntt o
off ttiim
me
e b
be
effo
orre
e T
Trra
an
ne
e
S
Se
errv
viicce
e a
arrrriiv
ve
ess tto
o d
do
o sstta
arrtt--u
up
p..
Check boxes if the task is complete or if the answer is
“yes”.
1. C
Ch
hiilllle
err
☐
Installation meets foundation requirements.
☐
In place and piped.
☐
Isolation pads or elastomeric pads installed
(optional).
☐
For units with InvisiSound™ Ultimate Option
(model number digit 12 = 3), compressor
mounting bolts have been removed.
2. R
Re
effrriig
ge
erra
an
ntt P
Prre
essssu
urre
e C
Ch
he
ecckk
☐
PRIOR to water being pumped into system, use
gauges to verify positive pressure in the
evaporator and condenser. Lack of pressure
could indicate a system leak. When charging in
the factory, approximately 95% of the
refrigerant charge is isolated in the evaporator,
and the other 5% is contained in the condenser
and compressor. In the event that no pressure is
present, contact local Trane service.
N
No
otte
e:: Verification must be done by gauges. Do NOT
rely only on values from unit transducers.
3. P
Piip
piin
ng
g
☐
Water piping flushed before making final
connections to the system
Chilled water piping connected to:
☐
Evaporator
☐
Air handling unit
☐
Pumps
☐
Flow switch or flow proving device
installed (if not factory provided)
☐
Strainer installed and cleaned
☐
Water supply connected to filling system
☐
Does unit have freeze inhibitor? If unit has
freeze inhibitor:
☐
Verify type and concentration correct per
unit submittal
☐
Calculate and record freeze point of the
solution: __________
☐
Systems filled
☐
Pumps run, air bled from system
☐
Strainer installed and cleaned
☐
Relief valve ventilation piping installed (if
applicable)
4. F
Fllo
ow
w b
ba
alla
an
ncciin
ng
g v
va
allv
ve
ess iin
nsstta
alllle
ed
d
☐
Leaving chilled water
5.
G
Ga
au
ug
ge
ess,, tth
he
errm
mo
om
me
ette
errss,, a
an
nd
d a
aiirr v
ve
en
nttss
☐
Installed on both sides of evaporator
6. W
Wiirriin
ng
g
☐
Wire size per submittal and NEC 310-16
☐
Full power available
☐
Interconnecting wiring, starter to panel (as
required)
☐
External interlocks (flow switch, pumps
auxiliary, etc.)
☐
Chilled water pump (connected and tested)
☐
115 Vac power available for service tools
☐
All controls installed and connected
7. T
Te
essttiin
ng
g
☐
Dry nitrogen available for pressure testing
☐
Trace gas amounts of R-134a available for leak
testing, if necessary
8. R
Re
effrriig
ge
erra
an
ntt o
on
n jjo
ob
b ssiitte
e ((iiff n
niittrro
og
ge
en
n cch
ha
arrg
ge
e
o
op
pttiio
on
n,, m
mo
od
de
ell n
nu
um
mb
be
err d
diig
giitt 1
15
5 =
= 2
2,, iiss cch
ho
osse
en
n))
9. S
Sy
ysstte
em
mss cca
an
n b
be
e o
op
pe
erra
atte
ed
d u
un
nd
de
err llo
oa
ad
d cco
on
nd
diittiio
on
nss