30
AC-SVX001A-EN
Table 11.
Elastomeric isolator selections
Unit
Size
Isolator Position
1
2
3
4
5
6
7
8
9
10
Standard Length Units
150
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Brown 61
Brown 61
-
-
165
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Red 62
Red 62
-
-
180
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Red 62
Red 62
-
-
200
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Black 60
Black 60
225
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Black 60
Black 60
250
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Black 60
Black 60
275
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Brown 61
Brown 61
300
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Brown 61
Brown 61
Extended Length Units
150
Green 63
Green 63
Green 63
Green 63
Green 63
Green 63
Brown 61
Brown 61
-
-
165
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
-
-
180
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
-
-
200
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
Brown 61
Brown 61
225
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
Brown 61
Brown 61
250
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
Brown 61
Brown 61
275
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
Brown 61
Brown 61
300
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Black 64
Brown 61
Brown 61
Compressor Mounting Bolt
Removal
U
Un
niittss w
wiitth
h IIn
nv
viissiiS
So
ou
un
nd
d™
™ U
Ullttiim
ma
atte
e O
Op
pttiio
on
n ((M
Mo
od
de
ell
N
Nu
um
mb
be
err D
Diig
giitt 1
12
2 =
= 3
3))
For chillers built with InvisiSound Ultimate option,
compressor mounting bolts must be removed to
assure minimum noise during operation. Use a 24mm
socket to remove the (3) M15 x 75mm mounting bolts
for each compressor. They are located under
compressor mounting feet. See figure below.
IIm
mp
po
orrtta
an
ntt::
•
DO NOT DISCARD MOUNTING BOLTS.
Store bolts in the control panel for
future use.
•
All mounting bolts MUST be reinstalled
prior to compressor removal or unit
move.
N
NO
OT
TIIC
CE
E
E
Eq
qu
uiip
pm
me
en
ntt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o rre
eiin
nsstta
allll b
bo
ollttss cco
ou
ulld
d cca
au
usse
e ssh
hiiffttiin
ng
g o
off
p
pa
arrttss a
an
nd
d rre
essu
ulltt iin
n e
eq
qu
uiip
pm
me
en
ntt d
da
am
ma
ag
ge
e..
D
Do
o n
no
ott rre
em
mo
ov
ve
e cco
om
mp
prre
esssso
orr o
orr m
mo
ov
ve
e u
un
niitt w
wiitth
ho
ou
utt
rre
ea
atttta
acch
hiin
ng
g cco
om
mp
prre
esssso
orr m
mo
ou
un
nttiin
ng
g b
bo
ollttss..
Figure 13.
Compressor mounting bolt removal
Compressor
Mounting Bolt
Compressor
Mounting
Foot
Isolator
Drainage
Locate the unit near a large capacity drain for water
vessel drain-down during shutdown or repair.
Evaporators are provided with drain connections. A
vent on top of evaporator waterbox prevents vacuum
by allowing air into evaporator for complete drainage.
All local and national codes apply.