Center of Gravity
Figure 10.
Center of gravity
END VIEW
(Non-Control Panel End)
Z
Y
CG
SIDE VIEW
X
CG
Control P
anel
Table 6. Center of gravity dimensions
Unit
Size
CGx
CGy
CGz
CGx
CGy
CGz
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
Standard Length Unit
Extended Length Unit
150
93.9
2384
44.2
1122
44.2
1124
128.2
3255
44.0
1118
43.3
1100
165
105.8
2686
44.2
1122
45.9
1166
139.1
3532
44.2
1124
44.9
1142
180
106.0
2691
44.5
1131
45.6
1159
139.6
3545
44.5
1129
44.7
1135
200
114.1
2898
44.1
1121
47.2
1199
147.2
3738
44.2
1124
46.3
1175
225
115.8
2941
44.1
1120
45.2
1148
148.8
3780
44.2
1122
44.4
1129
250
115.1
2924
44.1
1120
45.6
1158
149.0
3785
44.1
1121
44.8
1139
275
127.7
3242
44.0
1117
46.1
1172
162.3
4122
44.2
1122
45.4
1153
300
139.5
3544
44.0
1116
47.1
1197
174.3
4427
43.8
1113
46.4
1178
Isolation and Sound Emission
The most effective form of isolation is to locate the unit
away from any sound sensitive area. Structurally
transmitted sound can be reduced by elastomeric
vibration eliminators. Spring isolators are not
recommended. Consult an acoustical engineer in
critical sound applications.
For maximum isolation effect, isolate water lines and
electrical conduit. Wall sleeves and rubber isolated
piping hangers can be used to reduce the sound
transmitted through water piping. To reduce the sound
transmitted through electrical conduit, use flexible
electrical conduit.
State and local codes on sound emissions should
always be considered. Since the environment in which
a sound source is located affects sound pressure, unit
placement must be carefully evaluated. Sound power
levels for Stealth chillers are available on request.
Unit Isolation and Leveling
For additional reduction of sound and vibration, install
the optional elastomeric isolators.
Construct an isolated concrete pad for the unit or
provide concrete footings at the unit mounting points.
Mount the unit directly to the concrete pads or
footings.
Level the unit using the base rail as a reference. The
unit must be level within 1/4” (6.4 mm) over the entire
length and width. Use shims as necessary to level the
unit.
Elastomeric Isolators
N
No
otte
e:: See unit submittal, or tables in this section, for
point weights, isolator locations and isolator
selections.
1. Secure the isolators to the mounting surface using
the mounting slots in the isolator base plate. Do not
fully tighten the isolator mounting bolts at this time.
2. Align the mounting holes in the base of the unit
with the threaded positioning pins on the top of the
isolators.
3. Lower the unit onto the isolators and secure the
isolator to the unit with a nut.
4. Level the unit carefully. Fully tighten the isolator
mounting bolts.