RT-SVX060A-GB
18
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Installation
Instructions for the roofcurb assembly and installation
In order to insure watertighness of the roofcurb
assembly, it is important to respect the schematics
below and to consult the booklet for roofcurb assembly
shipped with the roofcurb module. Be sure that gasket is
positionned on the roofcurb and without damage before
unit positionning.
To avoid any property damage or personal injury, it
is the installer’s reponsibility to make sure that the
installation will not impair the function of this curb, or
the unit to be installed; and that the roofcurb and unit
must be completly sealed, preventing any water or air
leakage damage.
Figure 3 - Waterproofing
4
1
2
3
1. Roofcurb
2. Roof membrane
3. Seal
4. Rooftop
Installing the Unit
The structure accommodating the unit(s) must be
designed to support the equipment in operation, as
a minimum. Refer to submittals drawings supplied
with the unit for dimensions, weigth and clearance
requirement around unit.
Unit support
Install the unit on a flat foundation strong enough to
support unit loading and level (within 5 mm across
the length and width of the unit).If the unit is to be
roof mounted check the building codes for weight
distribution requirements
Location and clearances
Choose a location that will enable air to circulate
freely in the condenser coil and allow air to be
discharged above the fans. The clearance distances
for air circulation and maintenance are indicated in
the submittals drawings.
Placing and rigging
The rooftop units are designed to be installed outdoor
and must be positioned horizontally (vertical air
discharge off the condenser).
Slab mount
For ground level installation, the unit base should be
adequately supported and hold the unit near level.
In areas where snowfall is common, the unit must
be elevated enough to ensure that the bottom of the
outdoor coil is above the height of the expected snow
accumulation.
Where severely cold temperatures are a consideration,
elevation of the unit is again recommended to ensure
that defrost water does not create an ice build up that
will interfere with unit operation. In addition, runoff
water from roofs, etc... must not be allowed to fall on
the outdoor coil; any blockage of airflow through the
coil can be detrimental to unit operation and reliability.
The manufacturer suggests that the bottom of the
outdoor coil be raised 30cm above grade or roof to
prevent possible ice build-up problems.
The unit frame structure is not designed to be
supported by four points (mounting on spring isolators
for instance).
The unit must therefore rest on its whole base.