background image

RT-SVX060A-GB

36

4

UNT-PRC002-GB

Technical Data

FWD

08

12

20

30

45

Power supply

(V/Ph/Hz)

230/1/50

Capacities
Cooling capacity on water (1)

(kW)

5,2

8,3

15

18,8

30,1

Heating capacity on water (2)

(kW)

6,3

11,9

18,9

20,9

38,2

Fan motor

(type)

2 x direct drive centrifugal

Fan power input (3)

(kW)

0,23

0,46

0,65

1,04

1,51

Current amps (3)

(A)

1,1

2,2

3,1

4,7

5,5

Start-up amps

(A)

3,2

5,5

9,3

14,1

16,5

Air flow
minimum

(m

3

/h)

490

980

1400

1800

2700

nominal

(m

3

/h)

820

1650

2300

3000

4500

maximum

(m

3

/h)

980

1970

2600

3600

5400

Main coil
Water entering/leaving connections

(type)

ISO R7 rotating female

(Dia)

3/4"

3/4"

1 1/2"

1 1/2"

1 1/2"

Electric heater (accessory for blower only)
Electric power supply

(V/Ph/Hz)

230/1/50

230/1/50 or 400/3/50

400/3/50

400/3/50

400/3/50

Heating capacity

(kW)

2/4

8

10

12

12

Hot water coil (accessory for blower only)
Heating capacity (4)

(kW)

6,3

12

17,4

22,4

34,5

G2 filter (filter box accessory)
Quantity

2

2

2

2

2

Dimensions ( LxWxth)

(mm)

386x221x8

486x271x8

586x321x8

586*421*8

586*621*8

G4 filter (filter box accessory)
Quantity

-

2

2

2

2

Dimensions ( LxWxth)

(mm)

-

486x264x48

586x314x48

586*414*48

586*614*48

Condensate pump (accessory)

(type)

Centrifugal

Water flow - lift height

(l/h - mm)

24 - 500

Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)

(dB(A))

36/40/43

38/41/44

46/50/53

47/52/57

47/52/58

Sound power level (5)

(dB(A))

46/50/53

48/51/54

56/60/63

57/62/67

57/62/68

Unit dimensions
Width x Depth

(mm)

890 x 600

1090 x 710

1290 x 820

1290 x 970

1290 x 1090

Height

(mm)

250

300

350

450

650

Shipped unit dimensions
Width x Depth

(mm)

933 x 644

1133 x 754

1333 x 864

1333 x 1008

1333*1133

Height

(mm)

260

310

360

460

660

Weight

(kg)

32

46

61

76

118

Colour

galvanised steel

Recommended fuse size
Unit alone (aM/gI)

(A)

8/16

8/16

8/16

8/25

8/25

Unit with electric heater (gI)

(A)

16 (2kW),25 (4kW)

40 (230V),3*16 (400V)

3*20

3*25

3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

Hot Water Coil (HWC)

Figure 16 - Hot water coil location in the unit (Downflow 

and horizontal supply air flow

 

HWC applies when additional heat is required. Hot 
water comes from external boiler or other device. HWC 
provides heating with a coil located after indoor coil 
and offer full modulation heating control through the 
use of a 3 ways valve. Control is based on mixed air 
temperature and zone temperature.
Factory setting is given to heat pump operation. Hot 
water is called in addition. Priority can be switched on 
site.
Antifreeze opens the 3 ways valve when the coil 
temperature is closed to the freezing point ( 2°C).
In antifreeze mode, unit operating, indoor fan is stopped 
and the unit locked out in manual reset. Fresh air 
damper is closed and the modulating valve opens. The 
freeze protection works with manual reset.

Important notice: it is important that the pump 
circulating hot water is permanently working to avoid 
water to freeze in the coil. Otherwise, in order to 
prevent water from freezing in the coil period, it is 
recommended to use ethylene glycol. The service of a 
used can cause scaling deposits, erosion or corrosion. 
Insulation and proceed to heater wire installation on 
all the water piping likely to be exposed to freezing 
temperatures in order to avoid freeze up the coil and 
heat losses. The water distribution network must be 
fitted with vents in places where air is likely to be 
trapped.

Figure 17 - Glycol percentage recommendation curve

1 = Critical risks of freezing
2 = Efficient freeze protection
3 = Ethylene glycol
4 =  Propylene glycol 

% = Glycol percentage (mass concentration)

°C = Glycol or water temperature

Water connection dimensions and characteristics

Figure 18 - Hot water coil view and connections

The hot water coil is factory mounted and placed in the 
discharge section. Two holes are provided to connect 
the hot water coil. The tubes for entering and leaving 
water are equipped with a threaded female connection.

Figure 19 - Hot Water Coil Pressure Drop

0

50

100

150

200

250

300

350

400

450

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

Ai

r P

re

ss

ure

 D

ro

p

Airflow Rate (m3/h)

HOT WATER COIL AIR PRESSURE DROP

Options

Содержание Airfinity XL IC

Страница 1: ...RT SVX060A GB Installation Operation Maintenance Original instructions Airfinity XL Models IH IC Large Packaged Rooftop Units 140 to 220 kW...

Страница 2: ...460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 2...

Страница 3: ...57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 6...

Страница 4: ...in accordance with factory standard before shipment Warnings and Cautions Warnings and Cautions appear at appropriate sections throughout this manual Your personal safety and the proper operation of...

Страница 5: ...izes the possibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and...

Страница 6: ...is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water tempera...

Страница 7: ...62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20...

Страница 8: ...bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IC140 IC150 IC170 IC190 IC220 Cooling Mode Net Cooling Capacity 1 kW 140...

Страница 9: ...t with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x300 Disconnect swich unit with other...

Страница 10: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Страница 11: ...s Extra Lenght Extra weight 4 Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner H...

Страница 12: ...ies Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IH140 IH150 IH170 IH190 IH220 Cooling Mode Net Cooling Capacity 1 kW 139 8 153 6 162 7 187 1 201...

Страница 13: ...95 95 95 150 150 Disconnect swich unit with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x...

Страница 14: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Страница 15: ...s Extra Lenght Extra weight Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner Hig...

Страница 16: ...ilable for FWD30 and FWD45 Sound level L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit d...

Страница 17: ...ion The installation must conform to all local standards and regulations Reception of Units Unit Handling The unit is supplied on wooden blocks It is recommended to check the machine s condition upon...

Страница 18: ...min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installation Instructions for the roofcurb assembly and installation In order to insure watertighness of the roofcurb assembly it is i...

Страница 19: ...63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installatio...

Страница 20: ...tering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the...

Страница 21: ...64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installation Filter installation Access to the filter cells is done via the filter access door Filter sup...

Страница 22: ...on The airflow measurement option when selected is associated with an air differential pressure sensor which measures the pressure difference before the inlet nozzle and inside the inlet nozzle Unit a...

Страница 23: ...212 General Electrical Recommendations Electrical Parts When reviewing this manual keep in mind All field installed wiring must be in accordance with local regulations CE directives and guidelines Be...

Страница 24: ...outing inside control panel should be made case by case by installer WARNING Ground Wire All field installed wiring must be completed by qualified personnel All field installed wiring must comply with...

Страница 25: ...51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69...

Страница 26: ...51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 64...

Страница 27: ...D 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit...

Страница 28: ...47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shi...

Страница 29: ...57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequen...

Страница 30: ...t dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008...

Страница 31: ...46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 100...

Страница 32: ...L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 10...

Страница 33: ...speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65...

Страница 34: ...ture 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat excha...

Страница 35: ...inimize the overpressure in the building caused by the introduction of fresh air This option is typically used when the fresh air intake needed is between 40 to 50 of the nominal air flow or when the...

Страница 36: ...he measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coi...

Страница 37: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Electric Heater Electric heater are fitted on the supply fan discharge Heaters have two heatin...

Страница 38: ...galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving te...

Страница 39: ...diagram supplied with the unit for details The resolution of analog outputs reaches 10 ppm CO2 The information is then sent to the controller CH536 to control the opening position of the fresh air da...

Страница 40: ...eaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air f...

Страница 41: ...gn occupancy of the zone Occupied standby setpoint 0 6L s per m2 ASHRAE62 1 x Surface Occupied setpoint 4 72L s per person ASHRAE62 1 x DesignOccupants Occupied standby setpoint 2 Occupancy based vent...

Страница 42: ...ring diagrams and options shipped with the unit Unit is level with sufficient clearance all round Duct network is correctly sized according to the unit configuration insulated and water tight Condensa...

Страница 43: ...s required to Check the gas category Check the gas intake pressure on the gas valve Perform the combustion analysis to verify that the level of flue gases corresponds to the data contained in general...

Страница 44: ...ess panels to service the unit Failure to disconnect power before attempting any servicing can result in severe injury or death Air filters It is very important for the central duct system air filters...

Страница 45: ...1 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 5...

Страница 46: ...ment pre commission Configure unit control module Calibrate controls Check operational set points and performance Check operation of all safety devices Megger the motor compressor windings Check unit...

Страница 47: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Oil analysis Trane Oil Analysis is a predictive tool used to detect minor issues before they b...

Страница 48: ...e comfortable and energy efficient environments Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com...

Отзывы: