RT-SVX060A-GB
6
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Unit Model Number Description
Digit 1 - Manufacturing location
E = Epinal France
Digit 2 - Unit model
I = Airfinity
Digit 3 - Unit type
C = Cooling only
H = Reversible Heat pump
Digit 4-5-6 Unit size
140 = 140 kW
150 = 150 kW
170 = 170 kW
190 = 190 kW
220 = 220 kW
Digit 7 - Efficiency level
S = Standard efficiency
Digit 8 - Refrigerant
A = R410A Factory full refrigerant charge
8 = R410A Factory refrigerant pre charge
Digit 9 - Unit voltage
E = 400 V - 3 Ph - 50 Hz
Digit 10 - Design Sequence
Digit 11 - Design Sequence
Digit 12 - Auxiliary Heat
X = Without
W = Hot water coil
E = Electric heater
L = Modulating gas burner,126 kW
S = Modulating gas burner,160 kW
H = Modulating gas burner,194 kW
P = Preheat coil
Digit 13 - Gas type
X = Without
1 = Propane gas
2 = Natural gas (G20)
3 = Natural gas (G25)
Digit 14 - Airflow configuration
D = Down Supply & Down Return
H = Horizontal Supply & Horizontal Return
I = Down Supply & Horizontal Return
J = Horizontal Supply & Down Return
Digit 15 - Available static pressure
1 = Standard External Static Pressure
2 = High External Static Pressure
Digit 16 - Operating map (cooling mode)
A = Standard ambient
L = Low ambient
Digit 17 - Free cooling (Economizer)
A = Temperature control
B = Enthalpy control
X = Without (full recirculation)
Digit 18 - Heat Recovery Module
X = Without
R = Configured for Rotary Wheel
B = Configured for Rotary wheel high airflow
U = Energy Recovery Circuit EC fans
Digit 19 - Dehumidification
X = Without
A = Dehumidification control
Digit 20 - Outdoor coil treatment
B = Without
E = With
Digit 21 - Indoor coil treatment
1 = Without
2 = With
Digit 22 - Filtration
A = G4 (50 mm) filters
B = G4 (50 mm) + F7 (100 mm) filters
C = G4 (50 mm) + F9 (100 mm) filters
D = F5 (50 mm) + F7 (100 mm) filters
Digit 23 - Temperature Zone sensor
X = Without
A = Duct-mounted zone sensor
B = Wall mounted zone sensor
Digit 24 - Room User Interface
X = Without
A = Wall-mounted interface THS04
B = Conventional thermostat
C = Wall mouted interface PGD1
Digit 25 - CO2 sensor
X = Without
1 = CO2 sensor duct-mounted
2 = CO2 sensor wall-mounted
Digit 26 - Factory assigned
Digit 27 - Airflow Measurement
X = Without
A = Airflow measurement and display
Digit 28 - Dirty filter detection
X = Without
1 = With
Digit 29 - Network protection relay
X = Phase reversal protection
A = Phase reversal and asymmetry protection