RT-SVX060A-GB
47
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Oil analysis
Trane Oil Analysis is a predictive tool used to detect
minor issues before they become major problems. It
also reduces failure detection time and allows planning
for appropriate maintenance. Oil changes can be
reduced by half resulting in lower operating costs and a
lower impact on the environment.
Refrigerant analysis
This Service includes a thorough analysis for
contamination and solution upgrade.
It is recommended that this analysis be performed every
six months.
Trane Select Agreements
Trane Select Agreements are programs tailored to
your needs, your business and your application. They
offer four different levels of coverage. From preventive
maintenance plans to fully comprehensive solutions,
you have the option of selecting the coverage that best
suits your requirements.
5 years motor-compressor warranty
This Service will provide a 5 years part and labor
warranty for the motor compressor only.
This Service is only available for units covered by a
5 years Maintenance Contract.
Energy enhancement
With Trane Building Advantage you can now explore
cost effective ways to optimize the energy effi ciency of
your existing system and generate immediate savings.
Energy management solutions are not only for new
systems or buildings. Trane Building Advantage offers
solutions designed to unlock energy savings in your
existing system.
Additionnal services