Troubleshooting
56
VFDB-SVX001A-EN
LED Usage
Anybus gateway AB7678 is selected for communication
between Modbus RTU and Ethernet networks. See more
details at www.anybus.com
There are five LEDs on the gateway for Modbus RTU
status:
AFD Over Temperature
Powercell / Transfomer Over
Temperature
12258
AFD Over Temperature
Powercell / Transfomer Over
Temperature
14245
AFD Over Temperature
Powercell / Transfomer Over
Temperature
14247
AFD Over Temperature
Powercell / Transfomer Over
Temperature
14249
AFD General Failure
All other faults
AFD Gate Kill active
Table 6.
IOM Tracer AdaptiView and drive diagnostics
(continued)
Chiller Tracer
AdaptiView Diagnostic
MV Drive Diagnostic
Drive
Fault
LED
Color
Indication
Gateway Status Refer to the user manual for further details
Processing
Green
Processing message
Off
Not processing
Bus Error
Red
Bus error
Off
Normal operation
Bus Ready
Green
Normal operation
Red
Bus timeout error
Off
Bus not running
HW Status
Red
Configuration switch error
Off
-