Mechanical Installation
VFDB-SVX001A-EN
37
Affix Cabinets to Floor
Typical floor drawings show minimum clearance distance,
conduit openings, and mounting holes for anchor bolts, as
shown in below
and
.
Secure the cabinet to the channel steel base using M12 bolt
(recommended), lock washer, two flat washers, and a nut
as shown in
.
Optional: The cabinet can also be welded to the steel base
once it is securely bolted, if desired.
Each weld location should be 3.9 in. (100 mm) for every
39.4 in. (1000 mm). See Mounting Requirements in the
PowerFlex 6000T Drives Shipping and Handling Manual,
publication 6000-PC100 for further information on the
steel base and desired trench and mounting customer-
specifications.
Figure 27.
Secure the cabinets, B-frame
Secure with M6
hardware (8 places)
2-socket screw M6x16
Combination pillar
WARNING
Drive Mounting Instructions!
Failure to correctly anchor the cabinet could result in
death or serious injury and equipment damage. Refer to
Rockwell’s technical drawings and installation manual
for drive mounting instructions. Contact the area
Rockwell Automation sales office if you do not have
these documents.
Figure 28.
Bolt cabinet to steel base, B-frame
M16 bolt
Flat washer
Lock washer