Cabinet
VFDB-SVX001A-EN
17
A-Frame and B-Frame Notes
General Notes
Note:
Refer to
1. Connections are spaced horizontally with dimension/
location shown in the front view.
2. NEMA 1 enclosure.
3. Maximum remote distance between drive and chiller is
150 ft (45.72 m).
Cable Notes
1. Top entry conduit openings standard.
Important:
On A-Frame units with top entry and/or exit
for the power cables, 24 inches of clearance
on the left side is recommended for side
access. As a result, the recommended is to
mount the input starter cabinet on the right
side of the drive.
2. Field-configurable for bottom entry line power.
3. All cable connections are bolted type; lugs provided by
others.
4. Cable space designed for non-shielded cable or
shielded cable with prefabricated stress cones.
5. Maximum cable information refer to
and
Shipping Note
•
Mounted on a (500 lb [226.8 kg] max) wooden skid
with provisions for a fork truck. Lifting means also
supplied on top.
Table 3.
B-Frame weights
(a)
and heat rejection
SRRL
LINE VOLTAGE-
FREQUENCY
VFD
AMPS
Motor
HP
MAX HEAT
REJECTION
BTU/HR
MAX NUMBER AND SIZE OF CABLES (NEMA)
WEIGHT
LB
FIGURE
LINE TO INPUT
STARTER
INPUT STARTER
TO DRIVE PANEL
DRIVE PANEL
OUTPUT TO MOTOR
251 2300/2400V-60Hz
250
1180
119080
1200 kcmil 5KV or
8KV/phase
1200 kcmil 5KV or
8KV/phase
1200 kcmil 5KV or 8KV/
phase
10802
A
286 2300/2400V-60Hz
285
1314
134100
10802
A
251
3300V-50/60Hz
250
1623
144000
1200 kcmil 5KV or
8KV/phase
1200 kcmil 5KV or
8KV/phase
1200 kcmil 5KV or 8KV/
phase
12789
B
265
3300V-50/60Hz
265
1676
151840
12789
B
(a) Weights do not include 500 lb (226.8 kg) maximum shipping skid.