36
VFDB-SVX001A-EN
Mechanical Installation
Install Drive panel
Connect Shipping Splits
The standard A-frame for PowerFlex 6000T drives comes
fully assembled and does not require any shipping splits
The B-frame for PowerFlex 6000T drives are shipped in
two sections, the Isolation Transformer Cabinet and Power
Module/LV Control Cabinet. These two cabinets must be
connected after located in its final position. The cabinets
are connected together in 8 or 10 places (depending on the
drive rating), half along the front edge of the cabinet and
half along the rear edge of the cabinet. Access to the
interior of the cabinet is required to make these
connections. Access for the front connections requires
only opening the doors. Access for the rear connections
requires removing the back plates of the cabinet.
1. Arrange the sections as directed in the Dimensional
Drawings and move the sections together.
2. Align the cabinet side sheets together at the holes for
the hardware, refer to below figure.
3. Secure the cabinets together using M6 and M8
hardware.
Open the doors to access front edge joining holes (four
or five places).
Figure 26.
Align the cabinets, B-frame (6 kV shown)
Isolation Transformer Cabinet
Power Module/LV Control Cabinet
Table 1 - Sidesheet Openings
Front Wireway
U Phase Motor Cable
V Phase Motor Cable
4
W Phase Motor Cable
Ground Bus Connection
Voltage Sensing Board
Cables
7
Isolation Transformer
Cables Secondary
(1)(2)
(1) The number of Isolation Transformer secondary
cables is dependent on motor voltage class.
• 9 cables per motor phase (27 total) for 3/3.3 kV
• 12 cables per motor phase (36 total) for 4.16 kV
• 15 cables per motor phase (45 total) for 6 kV
• 18 cables per motor phase (54 total) of 6.6 kV
• 24 cables per motor phase (72 total) for 10 kV
• 27 cables per motor phase (81 total) for 11 kV
(2) 6/6.6 kV configurations only require 18 cable
hole locations per phase. Extra cable hole
locations allow for added installation flexibility.
1
3
4
5
6
2
Front
Front
7
Side View
7
7
5
6
3
2
1