Troubleshooting
54
VFDB-SVX001A-EN
Troubleshooting
This section can assist in field troubleshooting
Communicating MV drives, and can provide information,
which others can use to help you troubleshoot the drive.
1. Collect alarm and parameter information.
a. DO NOT cycle unit power or reset the controls.
Leave the AFD and the Symbio 800 in their present
states.
b. Record the “AFD Last Diagnostic Code” using
Tracer TU. This value is available under the Unit
Status tab, in the AF (Adjustable Frequency)
expanding box.
c. Record all Symbio 800 active and historic alarms.
Make a full chiller service report.
d. Document and check all applicable parameter
settings. This information can be verified off of the
chiller nameplate, and by referring to this manual.
2. Collect Chiller Information.
a. Note the following chiller information:
•
Operating mode and any sub-mode (i.e.,
100 percent or 75 percent load etc.)
•
Number of chiller starts, and hours of operation.
•
Time since last diagnostic shutdown (<1 minute,
<1 hour, >1 hour, etc.)
b. What was the chiller state at the time of the failure?
(Chiller starting? Running low load? Running full
load? etc.)
c. Record the chiller’s sales order and serial numbers,
and the drive’s serial and model numbers.
3. Troubleshooting
a. Note drive information and codes from drive
display.
b. Refer to the Rockwell manuals for further
troubleshooting information.
c. Contact Trane Service Company for assistance.
coordinates the chiller’s Tracer AdaptiView drive
diagnostics and the Rockwell MV drive diagnostics fault
and reference MV drive fault code. For additional
information on the faults, refer to the Rockwell PowerFlex
6000T MV AC Drive Technical Data section (Chapter 3) of
the manual that shipped with the drive. Only qualified
technicians should attempt any troubleshooting of the
drive and chiller. Contact your local Trane Service agency
to request service and/or additional support. Trane can
contact the appropriate technical service group for
additional support if necessary.
Table 6.
IOM Tracer AdaptiView and drive diagnostics
Chiller Tracer
AdaptiView Diagnostic
MV Drive Diagnostic
Drive
Fault
AFD Bus Over Voltage
OverVoltage
10107
AFD Bus Under Voltage
UnderVoltage
10106
AFD Bus Under Voltage
DC Bus Under Vltg
10209
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12510
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12511
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12512
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12513
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12514
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12515
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12516
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12517
AFD Bus Under Voltage
U0-U8_DCBusUnderVltg
12518
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12520
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12521
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12522
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12523
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12524
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12525
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12526
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12527
AFD Bus Under Voltage
V0-V8_DCBusUnderVltg
12528
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12530
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12531
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12532
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12533
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12534
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12535
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12536
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12537
AFD Bus Under Voltage
W0-8_DCBusUnderVltg
12538
AFD Ground Fault
L Ground Warning
13047
AFD Motor Current Overload Motor Overload
10003
AFD Motor Current Overload SW OverCurrent
10092
AFD Motor Current Overload Mtr OverCurrent
10218
AFD Motor Current Overload Drv Overcurrent
10216
AFD Motor Current Overload HW OverCurrent
10093
AFD Instantaneous Current
Overload
U0-U8/V0-V8/W0-W8 IGBT
Overcurrent
12150
AFD Instantaneous Current
Overload
U0-U8/V0-V8/W0-W8 IGBT
Overcurrent
12151
AFD Instantaneous Current
Overload
U0-U8/V0-V8/W0-W8 IGBT
Overcurrent
12152