Diagnostic Name Affects
Target
Severity
Persistence Active Modes
[Inactive Modes]
Criteria
Reset
Level
Comm Loss: Slide
Valve Load - xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Slide
Valve Unload - xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Step
Load - xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Econo-
mizer Valve – xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Econ-
omizer Discharge
Pressure – xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Econ-
omizer Discharge
Temp – xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Evapo-
rator Water Pump 1
Relay
Chiller
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Evapo-
rator Water Pump 2
Relay
Chiller
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Starter
xy
Cprsr
Immediate
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Local
Comm Loss: Speed
Command - xA
Cprsr
Normal
NonLatch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 15-30 second period.
Remote
Comm Loss: %RLA
Indication Output(-
Vdc)
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 15-30 second period.
Remote
Comm Loss: Local
BAS Interface
Chiller
Warning
NonLatch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful
communication is established with the
LonTalk LLID (LCIC) or BACnet LLID
(BCIC).
Remote
Comm Loss: Pro-
grammable Relay
Board 1
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Pro-
grammable Relay
Board 2
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: High
Pressure Cutout
Switch - xy
Cprsr
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Auxilia-
ry Setpoint Com-
mand
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 15-30 second period.
Remote
Comm Loss: Energy
Meter Pulse Input
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Ext
Noise Reduction
Request
Chiller
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 30 second period.
Remote
Comm Loss: Fan
Inverter Speed
Command
Circuit
Normal
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 15-30 second period.
Remote
Comm Loss: Fan
Inverter Speed
Command, Shared
Circuit 1 & 2
Circuit
Warning
Latch
All
Continual loss of communication be-
tween the MP and the Functional ID has
occurred for a 15-30 second period. This
is a warning, as it is conceivable that
the circuit may run without the center
shared fan deck working if there are
many other coils/fans on the circuits.
RTAG-SVX001H-EN
93
Remote