Figure 52
shows the timing from a stopped mode to energizing the
fi
rst compressor. The shortest allowable time
would be under the following conditions:
No motor restart inhibit time left from subsequent starts
Evaporator Water
fl
ow occurs quickly with pump on command
Need to cool (differential to start) already exists
The above conditions would allow a compressor to start in about 20 seconds.
Figure 52. Sequence of events: stopped to starting
RTAG-SVX001H-EN
73