There are four connections on the UC800 that support
the communication interfaces listed. See Figure 17 for
the locations of each of these ports.
BACnet® MS/TP
MODBUS™ Slave
LonTalk™ using LCI-C (from the IPC3 bus)
Comm 4 using TCI (from the IPC3 bus)
There are three rotary switches on the front of the UC800
controller. Use these switches to de
fi
ne a three-digit ad-
dress when the UC800 is installed in a BACnet or MOD-
BUS system (e.g., 107, 127, etc.).
Note:
Valid addresses are 001 to 127 for BACnet and 001
to 247 for MODBUS.
There are 10 LEDs on the front of the UC800.
Figure 22
shows the locations of each LED and
Table 26
describes
their behavior in speci
fi
c instances.
Controls
LED
UC800 Status
Marquee LED
Powered. If the Marquee LED is green solid,
the UC800 is powered and no problems exist.
Low power or malfunction. If the Marquee
LED is red solid, the UC800 is powered, but
there are problems present.
Alarm. The Marquee LED blinks Red when an
alarm exists.
LINK, MBUS, IMC
The TX LED blinks green at the data transfer
rate when the UC800 transfers data to other
devices on the link.
The Rx LED blinks yellow at the data trans-
fer rate when the UC800 receives data from
other devices on the link.
Ethernet Link
The LINK LED is solid green if the Ethernet
link is connected and communicating.
The ACT LED blinks yellow at the data trans-
Service
The Service LED is solid green when pressed.
use.
Important
:
Maintain at least 6 inches between low- volt-
age (<30V) and high voltage circuits. Fail-
ure to do so could result in electrical noise
that could distort the signals carried by the
low-voltage wiring, including IPC.
Information is tailored to operators, service technicians,
and owners. When operating a chiller, there is speci
fi
c
information you need on a day-to-day basis—setpoints,
limits, diagnostic information, and reports. Day-to-day
operational information is presented at the display. Log-
ically organized groups of information — chiller modes
of operation, active diagnostics, settings and reports put
information conveniently at your
fi
ngertips.
Figure 22. Wiring locations and connection ports
Table 26.
56
RTAG-SVX001H-EN