Unit
Size
Rated
Voltage
Unit Power
Conns
Motor Data
Compressor(Each)
Fan(Each)
Qty.
RLA
Comp1A,Comp1B/
Comp2A,Comp2B
XLRA Comp1A,Com-
p1B/ Comp2A,Com-
p2B
YLRA Comp1A,Com-
p1B/ Comp2A,Comp2B
Qty.
Ckt1/
Ckt2
kW FLA
225 380/60/3
1
2
203/203
1306/1306
424/424
6/6
1.5
3.8
225 460/60/3
1
2
168/168
1065/1065
346/346
6/6
1.5
3.8
230 380/60/3
1
2
203/203
1306/1306
424/424
7/7
1.5
3.8
230 460/60/3
1
2
168/168
1065/1065
346/346
7/7
1.5
3.8
285 380/60/3
2
4
170,203/203
1306,1306/1306
424,424/424
9/5
1.65
4.7
285 460/60/3
2
4
141,168/168
1065,1065/1065
346,346/346
9/5
1.65
4.7
310 380/60/3
2
4
203,203/203
1306,1306/1306
424,424/424
11/5
1.65
4.7
310 460/60/3
2
4
168,168/168
1065,1065/1065
346,346/346
11/5
1.65
4.7
340 380/60/3
2
4
203,203/203
1306,1306/1306
424,424/424
11/5
1.65
4.7
340 460/60/3
2
4
168,168/168
1065,1065/1065
346,346/346
11/5
1.65
4.7
375 380/60/3
2
4
170,203/170,203
1306,1306/1306,1306
424,424/424,424
9/9
1.65
4.7
375 460/60/3
2
4
141,168/141,168
1065,1065/1065,1065
346,346/346,346
9/9
1.65
4.7
400 380/60/3
2
4
203,203/203,203
1306,1306/1306,1306
424,424/424,424
9/9
1.65
4.7
400 460/60/3
2
4
168,168/168,168
1065,1065/1065,1065
346,346/346,346
9/9
1.65
4.7
440 380/60/3
2
4
203,203/203,203
1306,1306/1306,1306
424,424/424,424
10/10
1.65
4.7
440 460/60/3
2
4
168,168/168,168
1065,1065/1065,1065
346,346/346,346
10/10
1.65
4.7
460 380/60/3
2
4
203,203/203,203
1306,1306/1306,1306
424,424/424,424
14/14
1.65
4.7
460 460/60/3
2
4
168,168/168,168
1065,1065/1065,1065
346,346/346,346
14/14
1.65
4.7
Installation - Electrical
Notes:
1. RLA-Rated load amps
2. XLRA-Locked rotor amps are based on full winding starts
4. Customer need to provide an isolated power 230V/60Hz/1 to heat the Evaporator. For single circuit chiller,there are three heaters and
38
RTAG-SVX001H-EN
heaters total power is 1200W;For dual circuit chiller,there are four heaters and heaters total power is 1600W.
Table 13. Electrical data –PSE at all ambient operation