45
58
R
PE#11 configuration
uint16
none
Bit mask:
bit8 = if 1, the device is approved in the network
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel is in use
59
R
PE#11 status
uint16
none
Bit mask:
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel alarm is active
bit8…13 = PE unit channels CH1…CH6: if 1, the
channel alarm has been deactivated but not
acknowledged
60
R
PE#12 configuration
uint16
none
Bit mask:
bit8 = if 1, the device is approved in the network
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel is in use
61
R
PE#12 status
uint16
none
Bit mask:
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel alarm is active
bit8…13 = PE unit channels CH1…CH6: if 1, the
channel alarm has been deactivated but not
acknowledged
62
R
PE#13 configuration
uint16
none
Bit mask:
bit8 = if 1, the device is approved in the network
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel is in use
63
R
PE#13 status
uint16
none
Bit mask:
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel alarm is active
bit8…13 = PE unit channels CH1…CH6: if 1, the
channel alarm has been deactivated but not
acknowledged
64
R
PE#14 configuration
uint16
none
Bit mask:
bit8 = if 1, the device is approved in the network
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel is in use
65
R
PE#14 status
uint16
none
Bit mask:
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel alarm is active
bit8…13 = PE unit channels CH1…CH6: if 1, the
channel alarm has been deactivated but not
acknowledged
66
R
PE#15 configuration
uint16
none
Bit mask:
bit8 = if 1, the device is approved in the network
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel is in use
67
R
PE#15 status
uint16
none
Bit mask:
bit0…5 = PE unit channels CH1…CH6: if 1, the
channel alarm is active
bit8…13 = PE unit channels CH1…CH6: if 1, the
channel alarm has been deactivated but not
acknowledged
68
R/
W
Isolation transformer nominal
current, device parameter
uint16
A
Read and written in amperes. The register value 40
corresponds to 40A. The minimum, maximum and
interval values are in channels 69, 70 and 71.
69
R
Isolation transformer nominal
current, the lowest allowed
value of the device parameter
uint16
A
1
70
R
Isolation transformer nominal
current, the highest allowed
value of the device parameter
uint16
A
100
71
R
Isolation transformer nominal
current, the device parameter
resolution (jog)
uint16
A
1
72
R/
W
The type of the transformer’s
temperature sensor
uint16
none
0= NTC, 1=Pt100
73
R/
W
Operating mode of the current
loop
uint16
none
0= 4
–
20mA, 1=0
–
20mA
Содержание SUPERINTEND IM-01.IND
Страница 19: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 19 http www trafox fi ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 25: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 25 http www trafox fi ...
Страница 29: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 29 http www trafox fi ...