SYSTEM CONFIGURATION
The most sensible configuration order for the settings is as follows:
•
If a microSD memory card has been connected to the device, enable it
(SETUP
→
Mem Card: in use) and restart the device.
•
Set the correct time. (SETUP
→
Time)
•
Set the electrical network, load current measurement and isolation transformer
parameters (SETUP
→
Filter, Max Cap, TranSize, Nom.Cur)
•
Set the alarm parameters (SETUP
→
InsLimit, PrInsLim, Temp Lim, TsensTyp
(tarvittaessa Pt Calib), LoadLim, PEalarm%, AlarmDly). Remember to disable
TempLim if temperature measurement has not been connected and to disable
LoadLim if the load current measurement has not been connected.
•
Set the AUX. ALARM mask (SETUP
→
AUXalarm), which defines the faults that
cause the AUX. ALARM relay to trigger.
•
If the system has devices for medical locations, which are available as
accessories, configure them according to the Superintend IMD MED
–
Installation
and User Manual.
•
When needed, set the range for CLT-
01 unit’s current loop
output
(SETUP
→
LoopCurr)
•
When needed, set the TCP/IP parameters (SETUP
→
IP Settings)
A more detailed description of the configuration is provided in the Manual section “SETUP
menu”.