L2
kOhm]
limit value was changed from
L1
to
L2.
Insulation Prealarm ON [
N
kOhm][
L
kOhm]
The insulation pre-alarm
activated with value
N
,
whereas the limit value has
been
L.
Insulation Prealarm OFF
The insulation pre-alarm is no
longer active.
Insulation Prealarm Acknowledge
The insulation pre-alarm that is
no longer active was
acknowledged manually.
Alarm Limit changed [PreInsulation] [
L1
%]->[
L2
%]
The insulation resistance pre-
alarm limit value was changed
from
L1
to
L2.
System Parameter changed [Filter] [
F1
s]->[
F2
s]
Filter parameter was changed
from
F1
to
F2
.
System Parameter changed [Capacitance] [
C1
s]-
>[
C2
s]
Max Cap parameter was
changed from
C1
to
C2
.
OverTemperature ON [
N
C][
L
C]
The transformer temperature
alarm activated with value
N
,
whereas the limit value has
been
L.
OverTemperature OFF
The transformer temperature
alarm is no longer active.
OverTemperature Acknowledge
The transformer temperature
alarm was acknowledged
manually.
Alarm Limit changed [Temperature] [
L1
C]->[
L2
C]
The transformer temperature
limit value was changed from
L1
to
L2.
Temperature Sensor Type Changed to NTC
Temperature Sensor Type Changed to Pt100
The type of the transformer’s
temperature sensor was
changed.
Temperature Sensor Calibrated [
O1
ADP]->[
O2
ADP]
The transformer’s temperature
sensor of type Pt100 was
calibrated. The old offset value
is
O1
as AD points, and the
new measured offset value is
O2
.
Temperature Sensor Cut Alarm ON
The measuring circuit of the
transformer’s temperature
sensor is cut.
Temperature Sensor Cut Alarm OFF
The measuring circuit of the
transformer’s temperature
sensor recovered from an
outage.
Temperature Sensor Cut Alarm Acknowledge
The measuring circuit of the
transformer’s temperature
sensor recovered from an
outage. The alarm was
acknowledged manually.
Temperature Sensor Shortcut Alarm ON
The measuring circuit of the
transformer’s temperature
sensor short-circuited.
Temperature Sensor Shortcut Alarm OFF
The measuring circuit of the
transformer’s temperature
Содержание SUPERINTEND IM-01.IND
Страница 19: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 19 http www trafox fi ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 25: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 25 http www trafox fi ...
Страница 29: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 29 http www trafox fi ...