Examples of network connection In the upper Figure, the IM-01.IND unit is in
the middle of the chain, and in the lower Figure, it is at the end of the chain.
Terminators are installed in the green units.
Checklist for the installation of the bus:
•
No more than two RS-485 cables may be installed in any unit. Otherwise, the bus
does not form an uninterrupted chain but has branches.
•
The shields of the cables are connected to the SH terminal of each unit.
•
The twisted pairs are connected so that the A
–
B signals are in one pair and the
+12V
–
GNDs are in another pair.
•
A terminator is installed at both ends of the bus, in other words, to those units
that only have one of each wire. The CLT-01 and IM-01.IND units are equipped
with a jumper for this purpose.
•
There is always a terminator in only two devices per chain.