SYSTEM DESCRIPTION
IM-01.IND is a device with which the insulation resistance and capacitance of floating
electricity networks can be measured and monitored in industrial applications. CLT-01 is
an optional accessory, which sends
0…20 / 4…20 mA
standard current messages to the
current loop of its output in accordance with the insulation resistance measured by IM-
01.IND. The system can also be equipped with devices PEC-01, TC-01 and IC-01, which
have been developed originally for medical locations. With those devices, the continuity
of the PE wire can be measured and alarms can be presented outside the monitoring
device room. The devices for medical locations are discussed in more detail in the
Superintend IMD MED
–
Installation and User Manual.
INSTALLATION
PHYSICAL CONNECTION
The devices are connected to the electrical network, which may contain
dangerous voltage. The device may be installed by a trained electrical
engineering professional only. The device contains no user-serviceable parts
and must not be opened. Using the device in violation of these instructions
may compromise safety.
The IM-01.IND unit is the control unit of the system and is installed in the switchboard.
Two IM-01.IND devices may not be installed galvanically in the same network, for
example on the secondary side of the same transformer. The connection is performed as
presented in Figure 1. The installation and wiring should be performed in accordance
with standards IEC 60364 as well as EN 50110. The operating voltage connection of IM-
01.IND must always be equipped with a coupler or a line protection switch so that the
electricity supply can be disconnected for the duration of maintenance work, for
example. The location of the disconnectors must be clearly marked in the switchboard.
The coupler or line protection switch should also control a relay or contactor, which
separates the measuring wires from the network to be measured. The IM-01.IND device
is equipped with an internal 1 A fuse. In spite of this, the wires of the operating voltage
supply should still be protected with an external fuse. A suitable if the size is, for
example, 6 A. In a DC operating voltage supply, an external Schurter 0001.2503
(T800mA) fuse should be used.
DEVICE MOUNTING
The IM-01.IND and CLT-01 devices are intended for installation in a DIN TS35 rail in
accordance with standard IEC 60715. They are installed by inserting the upper edge of
the DIN TS35 rail in the groove intended for the DIN TS35 rail on the back of the device
and by pushing the bottom edge of the device backward until the retaining latch clicks
into place.
Содержание SUPERINTEND IM-01.IND
Страница 19: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 19 http www trafox fi ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 25: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 25 http www trafox fi ...
Страница 29: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 29 http www trafox fi ...