7.6.3.6 Attribute 0x68, Preset Value
Danger of physical injury and damage to property due to an actual value
jump during execution of the preset adjustment function!
The preset adjustment function should only be executed when the
measuring system is stationary, or the resulting actual value jump must be
permitted by both the program and the application!
Preset Value
is used to set the measuring system value to any position value within the
range of 0 to measuring length in increments
–1.
The output position value is set to the
Preset value
parameter, if the
Set_Attribute_Single
service is executed to this attribute.
Attr.-ID
0x68
Data type
ULINT
Access
Set / Get
Lower limit
0
Upper limit
Value within the range from 0 to programmed
measuring length in steps
– 1
Default
0
Preset value
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
CEx-65
2
7
- 2
0
2
15
- 2
8
2
23
- 2
16
2
31
- 2
24
-
-
-
-
COx-65
2
7
- 2
0
2
15
- 2
8
2
23
- 2
16
2
31
- 2
24
2
39
- 2
32
2
47
- 2
40
2
55
- 2
48
2
63
- 2
56
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x68
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #104
So that this attribute is saved permanently,
0x70 Accept
Parameter
must be
performed.
In order to ensure a safe acceptance of the instance attributes
● 0x0C, Direction Counting Toggle
● 0x65, Total Measuring Range
● 0x66, Number of Revolutions - numerator and
● 0x67, Number of Revolutions - divisor
changes must be first taken over by means of
0x70 Accept Parameter
. In a
further step the new
Preset value
can be written. If this value should be saved
permanently, thereafter
0x70 Accept
Parameter
must be performed.