Trouble-shooting and diagnostic facilities
Printed in the Federal Republic of Germany
©
TR-Electronic GmbH 1997, All Rights Reserved
03/04/2010
TR - ECE - BA - GB - 0009 - 08
Page 39 of 45
4.2.1.4 Master address
In this byte, the slave enters the station address of the first master to have sent a valid
parameterization message. If several masters access the bus simultaneously, their
configuration and parameterization information must coincide exactly in order to
ensure correct operation of the Profibus.
4.2.1.5 Manufacturer's identifier
In bytes 5+6, the slave enters the manufacturer-specific identification number, an
unambiguous number for each device type which is reserved and filed with the PNO.
The identifier number of the encoder is AAAB(h).
4.2.1.6 Length (in byte) of extended diagnosis
If additional diagnostic information is available, the slave enters the number of bytes
following the standard diagnosis here.