3.8.2.14 Commissioning function
This parameter defines the setting of the commissioning function. In the standard
setting "Off, no status" the encoder is compatible to encoders with version 3.x (further
details see Teach-In function).
Selection
•
Off, no status (V3.x), default
•
Off, with status
•
On, with status
3.8.2.15 Short diagnostic (16 byte)
With this parameter in the TR operation modes the number of diagnostic bytes can be
limited from 6+51 bytes to 6+10 bytes. Therefore the encoder can be operated also to
Profibus masters with older issue numbers in these modes.
Selection
•
No,
default
•
Yes
3.8.2.16 Limit switch lower and upper limit
Is the status switched on (see commissioning function) the encoder can inform the
master via a bit whether the actual value is within the limits.
It is valid:
Limit switch bit = 0
if lower limit < actual value < upper limit
Limit switch bit = 1
if actual value < lower limit or actual value > upper limit
The inputs depend on the total measuring length in increments.
•
Lower
limit
0
•
Upper limit
total measuring length in increments - 1
•
Default
value 0