Troubleshooting
Electrical Control
d. Protection of pressure or temp.
e. Open-circuit and short-circuit trouble of T3
Is connection to connector of temp. sensor good?
Check the resistance of the temp. sensor according to
Appendix 1
Repair connector
No
Yes
Is it the resistance is normal?
Indoor PCB is defective.
Replace the sensor
Yes
No
Protection of pressure or temp.
Is it k1 or K2 open ?
Is temp. protective switch K1 open
Possible reason
1. The wires is loose to K1
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor fan or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is leakage
Is pressure protective switch K2 open
Yes
Yes
Yes
Possible reason
1. The wires is loose to K2
2. Air or other gas in the refrigerant.
3. Heat exchanger is dirty
4. Outdoor motor or fan blade is
defective
5. Outdoor unit is in bad ventilation
6. Refrigerant is too much
Содержание CCT140A-M
Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...
Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...
Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...
Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...
Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...
Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...
Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...
Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...
Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...