Electrical Control Function
Electrical Control
1.3 Operation Modes and Functions
1.3.1 Fan mode
(
1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/(med)/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
Big Cassette
Compact Cassette
1.3.2 Cooling Mode
1.3.2.1 Outdoor fan running rules
For 1-phase outdoor units:
The On-off outdoor units have single fan speed. The outdoor fan will run following the compressor except
when AC is in evaporator high temp. protection in heating mode ,condenser high temp. protection in cooling
mode, defrosting mode and the current protection.
For 3-phase outdoor units:
33
30
High
Low
1.3.2.2 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, (medium), low and auto.
The auto fan:
Big cassette:
T1
High
27
°
C
24
°
C
Low
T1
High
27
°
C
25
°
C
Low
Содержание CCT140A-M
Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...
Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...
Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...
Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...
Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...
Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...
Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...
Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...
Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...