Electrical Control Function
Electrical Control
For high static pressure duct & cassette: The timer function will change the AC current operation mode.
Suppose users set the
“
timer off
”
function and AC is off now, the AC will turn on firstly and then turn off when
reaching the setting time.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 It is valid in cooling, heating and auto mode.
1.3.7.2. Turning off, changing mode or setting fan speed will cancel economy function.
1.3.7.3 Operation process in sleep mode is as follow:
After pressing ECONOMIC or SLEEP button on the controller, the machine will go into economy mode.
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every hour, 2 hours later the setting
temperature stops rising.
For heat pump models, when they are in heating, the setting temperature reduces 1
℃
(be higher than 17
℃
)
every hour, 2 hours later the setting temperature stops reducing.
1.3.7.4 In this mode, the fan speed is forced into AUTO mode.
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
1.3.9 Drain pump control(For Cassette)
1.3.9.1 Water level check
The water lever will be checked every 5 seconds, if the feedback signal is abnormal, it will be considered as
drain water full by the control system.
1.3.9.2 Drain pump control
If there is no water full error, the drain pump will be on when the unit is in cooling mode (including
auto-cooling and forced cooling) and dry mode. It will be off when the unit is in heating mode, fan only mode
or off state (if the pump is on before the unit is off, it will delay 3 minutes to be off).
If there is a water full error, the drain pump will be on when the error occurs. Afterwards:
If the error disappears in 3 minutes, the drain pump will work as normal state. (if it is necessary to turn off the
pump, it will be off in 1 minute delay.)
If the error is still there in 3 minutes, the drain pump will be off as well as the AC unit. The error can be
cleared only when the power of the unit is cut off.
Содержание CCT140A-M
Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...
Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...
Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...
Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...
Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...
Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...
Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...
Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...
Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...