Electrical Control Function
Electrical Control
Auto fan action:
For cassette:
1.3.3.3 Defrosting mode
:
For 1-phase outdoor units:
l
Condition of defrosting:
AC will enter defrosting mode if any of the following items is satisfied.
A: For DL, high static pressure duct & cassette :The compressor keeps running over 40 minutes and T3
<
-2
℃
For A5 duct: T3<0
℃
and the compressor keeps running over 45 minutes. Meanwhile T3
<
-3
℃
for
3minutes.
B: After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2 protection
cumulates up to 90 minutes.
l
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal
heating mode.
A: T3 rises to be higher than 20
℃
.
B: The machine has run for 10 minutes in defrosting.
l
Defrosting action
:
For A5 duct:
T1-TS
3
°
C Low
1
°
C High
T2
TE14+2
℃
TE14
Setting
Low for15s, then
off
Содержание CCT140A-M
Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...
Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...
Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...
Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...
Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...
Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...
Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...
Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...
Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...