Electrical Control Function
Electrical Control
For the others type::
The compressor is running, and 4-way valve and outdoor fan stop. The indoor fan works as anti-cold wind
procedure. When defrosting is over, the compressor keeps running and the 4-way valve and outdoor fan will
start up.
For 3-phase outdoor units:
l
Condition of defrosting:
T3<0
℃
and the compressor keeps running over 45 minutes. Meanwhile T3
<
-3
℃
for 3minutes.
l
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal
heating mode.
A: T3 rises to be higher than 20
℃
.
B: The machine has run for 10 minutes in defrosting.
l
Defrosting action
:
The compressor is running, and 4-way valve and outdoor fan stop. The indoor fan works as anti-cold wind
procedure. When defrosting is over, the compressor keeps running and the 4-way valve and outdoor fan will
start up.
Setting defrosting time
45S 45S
Compressor
4 way valve 40S
40S
Outdoor fan
Indoor fan
10S
Содержание CCT140A-M
Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...
Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...
Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...
Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...
Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...
Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...
Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...
Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...
Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...