Troubleshooting 

Electrical Control 

Appendix 1

 Temperature Sensor Resistance Value Table    (

--K) 

 

K Ohm 

 

K Ohm 

 

K Ohm 

 

K Ohm 

-20 

115.266 

20 

12.6431 

60 

2.35774 

100 

0.62973 

-19 

108.146 

21 

12.0561 

61 

2.27249 

101 

0.61148 

-18 

101.517 

22 

11.5000 

62 

2.19073 

102 

0.59386 

-17 

96.3423 

23 

10.9731 

63 

2.11241 

103 

0.57683 

-16 

89.5865 

24 

10.4736 

64 

2.03732 

104 

0.56038 

-15 

84.2190 

25 

10.000 

65 

1.96532 

105 

0.54448 

-14 

79.3110 

26 

9.55074 

66 

1.89627 

106 

0.52912 

-13 

74.5360 

27 

9.12445 

67 

1.83003 

107 

0.51426 

-12 

70.1698 

28 

8.71983 

68 

1.76647 

108 

0.49989 

-11 

66.0898 

29 

8.33566 

69 

1.70547 

109 

0.48600 

-10 

62.2756 

30 

7.97078 

70 

1.64691 

110 

0.47256 

-9 

58.7079 

31 

7.62411 

71 

1.59068 

111 

0.45957 

-8 

56.3694 

32 

7.29464 

72 

1.53668 

112 

0.44699 

-7 

52.2438 

33 

6.98142 

73 

1.48481 

113 

0.43482 

-6 

49.3161 

34 

6.68355 

74 

1.43498 

114 

0.42304 

-5 

46.5725 

35 

6.40021 

75 

1.38703 

115 

0.41164 

-4 

44.0000 

36 

6.13059 

76 

1.34105 

116 

0.40060 

-3 

41.5878 

37 

5.87359 

77 

1.29078 

117 

0.38991 

-2 

39.8239 

38 

5.62961 

78 

1.25423 

118 

0.37956 

-1 

37.1988 

39 

5.39689 

79 

1.21330 

119 

0.36954 

35.2024 

40 

5.17519 

80 

1.17393 

120 

0.35982 

33.3269 

41 

4.96392 

81 

1.13604 

121 

0.35042 

31.5635 

42 

4.76253 

82 

1.09958 

122 

0.3413 

29.9058 

43 

4.57050 

83 

1.06448 

123 

0.33246 

28.3459 

44 

4.38736 

84 

1.03069 

124 

0.32390 

26.8778 

45 

4.21263 

85 

0.99815 

125 

0.31559 

25.4954 

46 

4.04589 

86 

0.96681 

126 

0.30754 

24.1932 

47 

3.88673 

87 

0.93662 

127 

0.29974 

22.5662 

48 

3.73476 

88 

0.90753 

128 

0.29216 

21.8094 

49 

3.58962 

89 

0.87950 

129 

0.28482 

10 

20.7184 

50 

3.45097 

90 

0.85248 

130 

0.27770 

11 

19.6891 

51 

3.31847 

91 

0.82643 

131 

0.27078 

12 

18.7177 

52 

3.19183 

92 

0.80132 

132 

0.26408 

13 

17.8005 

53 

3.07075 

93 

0.77709 

133 

0.25757 

14 

16.9341 

54 

2.95896 

94 

0.75373 

134 

0.25125 

15 

16.1156 

55 

2.84421 

95 

0.73119 

135 

0.24512 

16 

15.3418 

56 

2.73823 

96 

0.70944 

136 

0.23916 

17 

14.6181 

57 

2.63682 

97 

0.68844 

137 

0.23338 

18 

13.9180 

58 

2.53973 

98 

0.66818 

138 

0.22776 

19 

13.2631 

59 

2.44677 

99 

0.64862 

139 

0.22231 

 

Содержание CCT140A-M

Страница 1: ...Service Manual MODEL CCT70A M CCT140A M...

Страница 2: ...e Four way Cassette Type 1 Features 2 Dimensions 3 Service Space 4 Wiring Diagrams 5 Air Velocity and Temperature Distributions Reference Data 6 Electric Characteristics 7 Sound Levels 8 Accessories 9...

Страница 3: ...enient for maintenance 1 2 3D screw fan technology 3D screw indoor fan technology reduces the air resistance increases the air volume and improves the heat exchange efficiency Operate quietly 1 3 Air...

Страница 4: ...pumping head is 750mm upmost It s convenient to install drainage piping under most space condition 1 5 LED display Digital LED interface makes the unit more elegant Normally display the setting temper...

Страница 5: ...way Cassette Type 2 Dimensions CCT70A M 4 install hanger Gas side Liquid side E parts box Pump inspect hole Drain hole C C T 1 4 0 A M 4 install hanger Gas side Liquid side E parts box Pump inspect h...

Страница 6: ...oom for installation and maintenance The ceiling is horizontal and its structure can endure the weight of the indoor unit The outlet and the inlet are not impeded and the influence of external air is...

Страница 7: ...Wiring Diagrams Four way Cassette Type Wiring Diagrams C C T 7 0 A M...

Страница 8: ...Wiring Diagrams Four way Cassette Type CCT140A M...

Страница 9: ...Air Velocity and Temperature Distributions Reference Data Four way Cassette Type 5 Air Velocity and Temperature Distributions Reference Data Airflowvelocity Temperature...

Страница 10: ...s Model Indoor Units Power Supply Hz Voltage Min Max MFA CCT70A M 50 220 240V 198V 254V 25 CCT140A M 50 380 415V 342V 418V 15 Remark MFA Max Fuse Amps A 7 Sound Levels 1 0m FOUR WAY CASSETTE TYPE Micr...

Страница 11: ...1 6 Binding tape 6 7 Soundproof insulation sheath 2 Drainpipe Fittings 8 Out let pipe sheath 1 9 Out let pipe clasp 1 10 Tightening band 20 11 Drain joint 1 12 Seal ring 1 Protect Pipe Fittings 13 Wal...

Страница 12: ...Phase 1 phase 3 phase Frequency and Voltage 220 240V 50Hz 380 415V 50Hz Circuit Breaker Fuse A 40 25 25 15 Indoor Unit Power Wiring mm 2 3 2 5 5 2 5 Indoor Outdoor Connecting Wiring mm 2 Ground Wirin...

Страница 13: ...Field Wiring Four way Cassette Type 10 Field Wiring Wiring chart MCC 24HRN1...

Страница 14: ...Field Wiring Four way Cassette Type CCT140A M...

Страница 15: ...Outdoor Units Outdoor Units Part 3 Outdoor Units 1 Dimensions 2 Service Space 3 Piping Diagrams 4 Wiring Diagrams 5 Electric Characteristics 6 Operation Limits 7 Sound Levels...

Страница 16: ...Dimensions Outdoor Units 1 Dimensions mm Model A B C D E F H CCT70A M 842 560 335 360 312 324 695...

Страница 17: ...Dimensions Outdoor Units mm Model A B C D E F H CCT140A M 900 590 378 400 330 340 1167...

Страница 18: ...Service Space Outdoor Units 2 Service Space More than 60cm More than 30cm More than 60cm More than 200cm Air inlet Air inlet More than 30cm Air outlet Wall or obstacle Maintain channel...

Страница 19: ...ANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room temp sensor T3 Condenser temp sensor ACCUMULATOR INDOOR OUTDOOR...

Страница 20: ...EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room temp sensor T3 Condenser temp sensor ACCUMULATOR INDOOR OUTDOOR T4 A...

Страница 21: ...Wiring Diagrams Outdoor Units CCT70A M...

Страница 22: ...Wiring Diagrams Outdoor Units CCT140A M...

Страница 23: ...Electric Characteristics Outdoor Units 5 Electric Characteristics Model Outdoor Unit Hz Voltage Min Max CCT70A M 220 240V 208V 253V CCT140A M 50 380 420V 342V 440V...

Страница 24: ...r temperature 18 43 7 24 7 43 For the models with low temperature cooling system 10 15 25 30 35 20 15 20 25 30 35 40 45 Indoor temperature WB Outdoor temperature DB STD Cooling 43 17 32 10 5 0 5 10 18...

Страница 25: ...s 7 Sound Levels 24000Btu h 48000Btu h Microphone Outdoor Unit H 1 0m Note H 0 5 height of outdoor unit Note The point A is in the middle of the whole outdoor panel Model Noise level dB A C C T 7 0 A...

Страница 26: ...Electrical Control Electrical Control Part 5 Electrical Control System 1 Electrical Control Function 2 Troubleshooting 3 Controller...

Страница 27: ...osed If it is open the system will stop until the fault is cleared During defrosting procedure and 4 minutes after defrosting ends low pressure switch won t be checked Note The system will not check i...

Страница 28: ...1 3 2 1 Outdoor fan running rules For 1 phase outdoor units The On off outdoor units have single fan speed The outdoor fan will run following the compressor except when AC is in evaporator high temp...

Страница 29: ...T2 keeps lower than TE5 for 3 minutes the compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up 1 3 2 4 Condenser high temperature T3 prot...

Страница 30: ...High 1 3 3 2 Indoor fan running rules When the compressor is on the indoor fan can be set to high med low auto And the anti cold wind function has the priority Anti cold wind function When evaporator...

Страница 31: ...compressor keeps running over 45 minutes Meanwhile T3 3 for 3minutes B After the last defrosting the time that the outdoor fan is off but the compressor is on in high T2 protection cumulates up to 90...

Страница 32: ...nwhile T3 3 for 3minutes l Condition of ending defrosting If any one of the following items is satisfied the defrosting will terminate and the machine will turn to normal heating mode A T3 rises to be...

Страница 33: ...nd the same as that in cooling mode 1 3 5 3 The louver operates the same as in cooling mode 1 3 6 Timer function 1 3 6 1 Timing range is 24 hours 1 3 6 2 Timer on The machine will turn on automaticall...

Страница 34: ...auto restart function which is carried out through an auto restart module In case of a sudden power failure the module memorizes the setting conditions before the power failure The unit will resume th...

Страница 35: ...ration Timer Def Fan Alarm Digital LED Display Malfunction or protection 1 X X X E2 Indoor temperature sensor is abnormal 2 X X X E3 Evaporator temperature sensor is abnormal 3 X X X E4 Condenser temp...

Страница 36: ...ter errors are eliminated For T3 malfunction of 5HP can t recover automatically 6 X X X Evaporator temperature sensor is abnormal 7 X X X Condenser temperature sensor is abnormal 8 X X EEPROM malfunct...

Страница 37: ...Flash Off Trouble Overload of current Off Off Flash Trouble Communication malfunction Flash Off Flash Trouble Open circuit and short circuit trouble of T3 Off Flash Flash Trouble Open circuit and sho...

Страница 38: ...connection to connector of temp sensor good Check the resistance of the temp sensor according to Appendix 1 Repair connector No Yes Is it the resistance is normal Indoor PCB is defective Replace the s...

Страница 39: ...broken Check PCB board or replace the main control board Replace the water level switch Yes No Check whether the water pump is normal Yes Insert the water level switch well No Yes Replace the water p...

Страница 40: ...se sequence error b Overload of current c Lack of phase Phase sequence error Change the order of two of the wires to power supply Switch on the unit again If the problem cannot be solved the outdoor P...

Страница 41: ...f pressure or temp Is it k1 or K2 open Is temp protective switch K1 open Possible reason 1 The wires is loose to K1 2 Air or other gas in the refrigerant 3 Heat exchanger is dirty 4 Outdoor fan or fan...

Страница 42: ...it normal Possible reason 1 Air or other gas in the refrigerant 2 Heat exchanger is dirty 3 Outdoor fan or fan blade is defective 4 Outdoor unit is bad ventilation 5 Refrigerant is leakage Replace th...

Страница 43: ...59 76 1 34105 116 0 40060 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1 37 1988 39 5 39689 79 1 21330 119 0 36954 0 35 2024 40 5 17519 80 1 17393 120 0 3598...

Страница 44: ...3 Co ol heat Lock Reset 15 13 12 14 Confirmbutton 1 6 Economic operation TIME ON TI ME OF F C LOCK SWING AIRDIRE CTI ON O K ECO SW ING MODE FAN S P EED M AUTO COO L DRY HEAT FAN TEMP SET SET Visual ph...

Страница 45: ...etting or electrifying for the first time Press CLOCK for 5s icon indicating hour will flash with 0 5s Press it again icon indicating minute will flash with 0 5s and are used to adjust the figure Sett...

Страница 46: ...er is standard for Four way cassette type and the Ceiling floor type General Function for wireless remote controller Model RG51Q1 BGE Rated voltage 3 0V 2pieces of LR03 7 batteries Min voltage for sen...

Страница 47: ...he current setting and reset remote controller 7 ON OFF For turning on or turning off the air conditioner 8 FAN SPEED Fan speed will be selected in following sequence once pressing this button AUTO LO...

Страница 48: ...MER ON then adjust the time of TIMER ON as 0 0 3 Timer off button Push the button to set TIMER OFF each time you push the button the time moves forward by o 5 hours When the set time is over 10 hours...

Страница 49: ...he icon of LOCK disappears In the mode of LOCK all the buttons are invalid except for LOCK button 5 CLOCK display Usually display the clock set currently Press the button CLOCK for 4 seconds the HOUR...

Страница 50: ...indoor unit and fixing a infrared emitter whose anode and cathode connecting with A and B near the receiver in the Indoor Unit Switch Board then connecting the terminal 5v GND Run in the Switch Board...

Отзывы: