Fig. #39
NOTE: The vent must not exceed a total length of 68 feet. Any
combination of rise and run may be used but must be constrained
to the boundaries of this chart. A total of 3 - 90° elbows or
combination of other elbows equalling 90° can be used without
reducing horizontal run. For each additional 90° elbow, or an
equal combination of elbows, reduce horizontal vent run by 2
feet. Ensure vent pipe is properly supported.
* 68 1/2”
** All dimensions are approximate. Both rise and run may vary with different
combinations of pipe.
24" Pipe
length
minimum
A
Minimum rise
B
Pipe length
C
Maximum run
D
Pipe length
Max.
68 1/2”
1-24”
20 1/2"
1-12"
72 3/4”
1-12” 1-18"
75 3/4"
1-48" 1-12"
78 3/4”
1-24" 1-12”
11' 2"
2-48" 1-24"
84 3/4”
1-24” 1-18"
15' 10 1/2"
3-48" 1-24"
1-12"
92 1/2”
1-48”
20’ 10 1/2”
5-48"
For other rise/run combinations see chart below
**
23
TC36.CE3 250313-48
Wall Termination Venting Chart