29 3/4"
24"
4“
*
CEILING
ADJACENT WALL
OR MANTEL SUPPOR
T
6”
COMBUSTIBLE FL
OOR
COMBUSTIBLE HEAR
TH
Figure 3: TCWS54STOK Minimum mantel clearances.
100001140
UNIT MAY BE RECESSED UP TO 4 1/2” WITH
NONCOMBUSTIBLE MASONRY TYPE MATERIAL
Minimum Clearances:
Side standoffs ....................................................... 0 in.
(0 mm)
Back standoffs ...................................................... 0 in.
(0 mm)
Top standoffs ......................................................... 0 in.
(0 mm)
Bottom of appliance .............................................. 0 in.
(0 mm)
Adjacent side wall ................................................. 4 in.
(102 mm)
Ceiling to appliance ............................................. 24 in.
(610 mm)
*Mantel to appliance ...............................See Figure #2
**Maximum Mantel extension .................See Figure #2
Mantel support ...................................................... 4 in.
(102 mm)
Vent pipe ...................................................... 1 3/4" in.
(45 mm)
* MANTEL CLEARANCE
A
9”
B
6”
C
3”
** MANTEL DEPTH
D
12”
E
6 3/4”
F
1 1/2”
MANTEL CLEARANCE
CHART
MAY USE COMBUSTIBLE
FACING MATERIAL IN THIS AREA
NON-COMBUSTIBLE
FINISH MATERIAL
SEE FIG #11& 12
NON-COMBUSTIBLE ZONE.
DO NOT INSTALL ANY COMBUSTIBLE MATERIAL,
ELECTRICAL WIRING OR GAS PLUMBING IN THIS
AREA.
COMBUSTIBLE FRAMING AND
FINISH WALL ABOVE STANDOFFS
STEEL FRAMING
FIREPLACE FRONT
TOP OF LINTEL BAR
A
B
C
D
E
F
Figure 2: TCWS54STOK Mantel clearances.
6
TCWS54STOK_270619-56
Minimum Clearances to Combustible Material